3.3
Commissioning
3.3.1
Setting the flush
The smallest possible flush volume must be set at the drain
valve in the cistern.
The flush volume is set via the DIP switches of the control.
1
2
3
4
5
6
7
8
"
#
$
A Setting of the flush volume
B Interval of the Viega function
C Setting the flush volume of the Viega function
0 DIP switch position: OFF
1 DIP switch position: ON
The assignment of the DIP switches:
n
Switches 1-4 define the flush volume.
n
Switches 5-7 define the interval of the Viega function.
n
Switch 8 defines the flush volume of the Viega function.
Handling
WC flush plate for Prevista Visign for More 204 electronic