Installation

The wiring diagrams in the manual should be followed carefully. heavy duty
conductors on wiring diagrams are shown heavily outlined, These wires
should be doubled up.

Lock release back EMF protection : 

A diode must be fitted across the

terminals on the lock release to suppress back EMF voltages. The diagram
below shows the polarity of the diode when fitted to the release.

+

-

1N4002

+

-

12V DC

LOCK RELEASE

DIODE

Cable size and type : 

When running cables for any intercom system, these

cables must be installed separately from the mains cables. All multipair
cables should be to CW1308 specification.  (0.5mm twisted pair telephone
cable). Max resistance = 10 Ohm.
Lock release wires should be doubled up. Max resistance = 3 Ohm
The cables sizes above can be used for distances up to 100m. On distances
above 100m the cable sizes should be increased to keep the overall
resistance of the cable below the RESISTANCES indicated above.

Safety Note : 

The earth wire from the cabinet lid should be connected to the

cabinet base and then to the earth connection in the building. This should be
checked for continuity.

Testing the installation :-

Check all the connections have been made correctly and then power up.
Call all the apartments in turn. Check for call tone to the apartment, speech in
both directions and lock release.
If the volume of speech needs to be adjusted, this can be done by adjusting
the presets on the rear of the amplifier at the door panel. (Repeat the above
for door two).
If the call tone volume needs adjusting this can be done at each handset
(Jumper marked VOL).
Check the fireman switch (If fitted).
Set the time clock on, off times. Check the trade button only works when the
time clock is on.

Содержание 524MS

Страница 1: ......

Страница 2: ...E 9 ISOLATION PCB DESCRIPTION PAGE 10 INSTALLATION TESTING PAGE 11 TELEPHONE CHART PAGE 12 ACCESSORIES DIAGRAM PAGE 13 WIRING DIAGRAM VR PANEL PAGE 14 WIRING DIAGRAM ISOLATION PAGE 15 WIRING DIAGRAM 3...

Страница 3: ......

Страница 4: ...ension strobe Battery discharge cut off PCB Isolation PCB Video VproX proximity system The sentry 1 system is a two door functional door entry system which can be expanded to control more doors with t...

Страница 5: ...and the camera and will be fitted within the control cabinet Operation A call will be activated by a visitor pressing the desired flat number on the door panel A timed call tone will be heard at the o...

Страница 6: ...PCB includes a link option JPR1 which when in position A the system will only allow one call to be activated at anyone time The system must time out before another call can be registered When the lin...

Страница 7: ......

Страница 8: ...CH PHONE CONNECTION 4 T CALLTONE TO PHONES 5 P LOCK TRIGGER FROM PHONES 7 NEGATIVE TO PHONES 12V 12 VOLTS SUPPLY TO PHONES JP5 TC1 TRADE BUTTON FOR DOOR ONE TC1 TRADE BUTTON FOR DOOR ONE TC2 TRADE BUT...

Страница 9: ......

Страница 10: ...either A B C or D When one of these outputs goes high i e with a call to that output a thyristor on the isolation PCB is triggered which in turn energises the relays for that handset Each of the four...

Страница 11: ...n be used for distances up to 100m On distances above 100m the cable sizes should be increased to keep the overall resistance of the cable below the RESISTANCES indicated above Safety Note The earth w...

Страница 12: ......

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ...12V DC when a call is activated Handset rings for only 1 second Check terminal 1 of the amp for continuity back to the sentry 1 PCB Check terminal 1 of the handset for continuity back to the sentry 1...

Страница 22: ......

Страница 23: ......

Страница 24: ......

Отзывы: