During initial power-up, the red and green LEDs will blink
synchronously once every 5 seconds. It will take approximately
20 seconds for the detector to finish the power-up cycle (see
Table 1).
Green LED
Red LED
Piezoelectric Horn
Power-up
Blinks every 5 sec
Blinks every 5 sec
Off
Normal (standby)
Blinks every 10 sec
Off
Off
Out of sensitivity
Off
Blinks every 5 sec
Off
Smoke Alarm
Off
Blinks every 1 sec
Temporal Pattern
Low Battery
Off
Blinks every 45 sec
Chirp every 45 sec
After power-up has completed and the detector is functioning
normally within its listed sensitivity range, the green LED blinks
once every 10 seconds.
If the detector is in need of maintenance
because its sensitivity has shifted outside the listed limits, the red
LED blinks once every 5 seconds.
When alarm has been activated by smoke, the red LED blinks
every 1 second. The LED indication must not be used in place of
the tests specified under Testing.
If the detector senses a low battery condition, the red LED blinks
once every 45 seconds.
Low Battery Detection
The SD is powered by a single 3-volt CR123A or DL123A Lithium
battery (included). The detector checks for a low battery at least
every 65 minutes. If a low battery is detected, the transmitter
sends a low battery message to the control panel, which
displays a low battery message and forward it to the monitoring
station.
In addition, the red LED of the SD will blink and the horn will
chirp every 45 seconds and the test switch alarm function
will be disabled. Pressing the test switch during this time will
silence the chirps for 12 hours. The battery should be replaced
BEFORE the chirps begin. Be sure to replace the battery with
a fresh one.
Battery Installation and Replacement
To replace the battery:
1. Remove the detector from its mounting base by twisting
the detector counterclockwise. Remove the battery, and
dispose properly.
2. To ensure proper power-down sequence, wait a minimum
of 20 seconds before installing new battery.
3. Install a new approved 3-volt Lithium battery in the
battery compartment. Follow the polarity diagram inside
the compartment.
4. Reinstall the smoke detector onto the mounting base by
turning the detector clockwise.
5. The green LED should blink about once every 10 seconds
to indicate normal operation. If the battery is not installed
correctly, the smoke detector will not operate and the
battery may be damaged. If the detector does not appear
to be sending a signal during any of the tests, check for
correct battery installation and for a fully charged battery.
Programming
The smoke detector must be enrolled in the control panel before
it can operate in the system.
Table 1: Detector LED Modes
Recording of the detector
The alarm panel must be put in "Recording device
mode", and the keypad must display “
PRESS
PROGRAM BUTTON OF DEVICE”.
Insert the CR123 lithium battery.
Press the TEST SWITCH of the detector
and wait feedback on the keypad.
With the aid of the keypad, continue
recording by running the Radio Range Test
>
Possibility of testing the RF range.
1
2
3
I N S T A L L A T I O N I N S T R U C T I O N
Smoke Detector
SD
SD means SD600 for USA/Canada and SD200 for Europe and rest of
the world.