9. Error indication
Error nr
Description
Possible cause
Solution
1
battery temperature
too high
Overcharging or fast charging
Check air flow near the battery Improve
cooling of environment. The charger
stops automatically and will resume once
the battery has cooled down
2
battery voltage too
high
Wiring mistake, or another charger
is over charging
Check all charging equipment.
Check cables and connections
3, 4, 5
temp. sense error
Wiring mistake or temperature
sensor broken
Check the temperature sensor wiring and
if that doesn’t help replace the
temperature sensor
6, 7, 8, 9
voltage sense error
Wiring mistake
Check the voltage sensor wiring.
17
charger temperature
too high
The heat generated by the charger
cannot be removed
Check air flow of the cabinet.
Improve cooling of environment.
The charger stops automatically and will
resume once the charger has cooled
down.
18
Internal error
Contact your dealer
20
charger bulk time
expired
After 10 hours of bulk charging, the
battery voltage has still not reached
the absorption voltage.
Possible cell failure or higher charge
current needed.
24
Fan failure
This error indicates that the fan is
powered on but the circuit does not
measure any current draw by the
fan. Most likely the fan is either
broken or obstructed.
Contact your dealer
34
Internal error
Contact your dealer
37
No input voltage
(only for the three
output version)
Mains removed or ac-input fuse
blown
Check mains availability and fuse.
65
charger disappeared
during operation
One of the other chargers with which
this charger was synchronizing has
disappeared during operation
To clear the error, switch the charger off
and back on.
66
Incompatible device
The charger is being paralleled to
another charger that has different
settings and/or a different charge
algorithm
Make sure all settings are the same and
update firmware on all chargers to the
latest version.
67
BMS connection lost
Connection to the BMS lost
Check the VE.Can bus cabling. When the
charger needs to operate in standalone
mode again, go to the setup menu #31
(BMS Present) and set to N.
113, 114
Internal error
Contact your dealer
115
Communication error
Check wiring and terminators
116, 117,
118
Internal error
Contact your dealer
119
Settings invalid
Restore defaults in the setup menu #62.