![Victron energy Skylla-i 24/100 Скачать руководство пользователя страница 9](http://html.mh-extra.com/html/victron-energy/skylla-i-24-100/skylla-i-24-100_manual_1014738009.webp)
9
EN
NL
FR
DE
ES
A
ppendi
x
3.1. Rotary switch
The rotary switch provides the user with a selection of preset battery types to be charged. See table below.
Warning: the charge voltages as given below are indicative only. Always refer to the battery supplier for the right
charge voltages.
Pos
Description
Absorption
Float
Storage
Equalization
dV/dT
V
V
V
maxV@% of Inom
mV/°C
0
Do not use
1
Gel Victron long life (OPzV)
Gel exide A600 (OPzV)
Gel MK
28,2
27,6
26,4
31,8@8% max 1hr
-32
2
Default setting
Gel Victron deep discharge, Gel Exide A200
AGM Victron deep discharge
Stationary tubular plate (OPzS)
Rolls Marine (flooded), Rolls Solar (flooded)
28,8
27,6
26,4
32,4@8% max 1hr
-32
3
AGM spiral cell
Rolls AGM
29,4
27,6
26,4
33,0@8% max 1hr
-32
4
PzS tubular plate traction batteries or
OPzS batteries in cyclic mode 1
28,2
27,6
26,4
31,8@25% max 4hrs
-32
5
PzS tubular plate traction batteries or
OPzS batteries in cyclic mode 2
28,8
27,6
26,4
32,4@25% max 4hrs
-32
6
PzS tubular plate traction batteries or
OPzS batteries in cyclic mode 3
30,0
27,6
26,4
33,6@25% max 4hrs
-32
7
Lithium Iron Phosphate (
LiFePo
4
) batteries
28,4
n. a.
26,7
n. a.
0
8
Adjustable: maximum charge current and
absorption and float voltages can be set with
potentiometers
Adj.
Adj.
26,4
(Vabs. + 3,6V)@25%
max 4hrs
-32
9
Power supply mode
24,0
n. a.
n. a.
n. a.
0
3.2. DIP switch
The DIP switches are numbered 6 to 1,
top to bottom
.
Default settings:
DS-6 Bulk Protection
on
DS-5 Absorption time
off
DS-4 Absorption time
on
DS-3 Adaptive
on
DS-2 Watch
on
DS-1 Automatic equalization
off
3.3. Explanation of settings:
DS-6. Bulk Protection.
When switched on, the failure LED will be lit and the charger will shut down when the bulk time exceeds
10 hrs.
DS-5 and DS-4. Absorption time.
The combination of switches 5 and 4 sets the maximum absorption time in case of adaptive
charging, and a fixed time in case the adaptive mode has been switched off (DS-3).
DS-5
DS-4
Absorption time
Off
Off
2 hrs (preferred for
LiFePo
4
batteries)
On
Off
4 hrs.
Off
On
8 hrs.
(default)
On
On
12 hrs.
DS 3. Adaptive.
When switched on, the absorption and float time depend on the bulk time (with the maximum time set by DS-5
and DS-4).
The dependencies are as follows:
Absorption time = (bulk time)*20 with a minimum of 30 minutes and a maximum as set by DS-5 and DS-4.
Float time = (bulk time)*20 with a minimum of 4hrs and a maximum of 8hrs.
DS-2. Watch.
When DS-2 is on, the battery voltage is checked when the charger is switched on. If the voltage exceeds 26V, the
charger will consider the battery fully charged, and start in storage mode. If the voltage is lower, the charger will start in bulk
mode.
When DS-2 is off, the charger will always start in bulk mode.
Содержание Skylla-i 24/100
Страница 2: ......
Страница 16: ......
Страница 73: ...1 EN NL FR DE ES Appendix Appendix A Dimensions ...
Страница 74: ...2 Appendix B Wall mounting bracket ...