2. Troubleshooting
2.1 The flash sequence table
Your Phoenix inverter is equipped with a self-diagnosis system, to inform you about
the cause of inverter shut down.
In the table below you can find out what kind of flashing sequence belongs to which
error.
2.2 Troubleshooting guidelines
PROBLEM : Inverter is not working (LED OFF)
Possible cause :
Remedy :
Power switch in OFF position.
Push the power switch to the ON
position.
Poor contact between the inverter’s
battery wires and the battery terminals.
Clean battery terminals or inverter wire
contacts. Tighten battery terminal
screws.
Blown inverter fuse.
The inverter has to be returned for
service.
Very poor battery condition.
Replace battery.
PROBLEM : ‘Battery voltage too low or too high’ error keeps on appearing
Possible cause :
Remedy :
Poor battery condition.
Replace battery or charge it first.
Poor connection or inadequate wiring
between battery and inverter,
resulting in too much voltage drop.
When extending the battery wires of the
inverter make sure you use the correct
wire gauge (
≥
1.5 times larger than the
fixed battery wires). It’s not advisable to
extend the battery wires to more than 3
meters.
General failure in your electrical
system (in case of no direct battery
connection).
Check your electrical system or consult
an electrical engineer to check it for
you.
LED
Status
Solid green
OK
Red, blinking fast
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
Over voltage
Red, blinking slow
Under voltage
Red, intermittent blinking
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
Over temperature
Solid red
Overload