8. TECHNICAL SPECIFICATIONS
MultiPlus-II 12/3000/120-50 2x120V
12/3000/120-50 2x120V
PowerControl & PowerAssist
Yes (on L1 input)
Transfer switch
50
Maximum AC input current
50A (each legs)
INVERTER
DC Input voltage range
9,5 – 17 V
Output when in inverter mode
Output voltage: 120 VAC ± 2%
Frequency: 60 Hz ± 0,1% (1)
Cont. output power at 25°C (3)
3000 VA
Cont. output power at 25°C
2400 W
Cont. output power at 40°C
2200 W
Cont. output power at 65°C
1700 W
Maximum apparent feed-in power
2500 VA
Peak power
5500 W
Maximum efficiency
93%
Zero load power
19 W
Zero load power in AES mode
15 W
Zero load power in Search mode
4 W
Maximum output current
60A peak, 50Arms for 1sec.
CHARGER
AC Input
Split phase: 180-280 VAC 45 – 65 Hz
Single phase: 90-140 VAC 45 – 65 Hz
Charge voltage 'absorption'
14,4 V
Charge voltage 'float'
13,8 V
Storage mode
13,2 V
Maximum battery charge current (4)
120 A
Battery temperature sensor
Yes
GENERAL
Auxiliary output
Yes (32 A)
External AC current sensor (optional)
100 A
Programmable relay (5)
Yes
Protection (2)
a – g
VE.Bus communication port
For parallel and three phase operation, remote monitoring
and system integration
General purpose com. port
Yes, 2x
Remote on-off
Yes
Operating temperature range
-40 to +65°C (fan assisted cooling)
Humidity (non-condensing)
max 95%
ENCLOSURE
Material & Colour
Steel, blue RAL 5012
Protection category
IP22
Battery-connection
M8 bolts
MultiPlus-II 12|3000|120-50 2x120V
Page 24