11
5. Configuration
•
Settings may only be changed by a qualified electrical engineer.
•
Read the instructions thoroughly before implementing changes.
•
During setting of the charger, the AC input must be removed.
5.1 Standard settings: ready for use
On delivery, the MultiPlus is set to standard factory values. In general, these settings are suitable for single-unit operation.
Warning:
Possibly, the standard battery charging voltage is not suitable for your batteries! Refer to the manufacturer's
documentation, or to your battery supplier!
Standard MultiPlus factory settings
Inverter frequency
50 Hz
Input frequency range
45 – 65 Hz
Input voltage range
180 – 265 VAC
Inverter voltage
230 VAC
Stand-alone / parallel / 3-phase
stand-alone
AES (Automatic Economy Switch)
off
Ground relay
on
Charger on/ off
on
Battery charge curve
four-stage adaptive with BatterySafe mode
Charging current
75 % of the maximum charging current
Battery type
Victron Gel Deep Discharge (also suitable for Victron AGM Deep Discharge)
Automatic equalisation charging
off
Absorption voltage
14.4 / 28.8 / 57.6 V
Absorption time
up to 8 hours (depending on bulk time)
Float voltage
13.8 / 27.6 / 55.2 V
Storage voltage
13.2 / 26.4 / 52.8V (not adjustable)
Repeated absorption time
1 hour
Absorption repeat interval
7 days
Bulk protection
on
AC input current limit
50 A or 16 A depending on model (= adjustable current limit for PowerControl and
PowerAssist functions)
UPS feature
on
Dynamic current limiter
off
WeakAC
off
BoostFactor
2
Programmable relay
alarm function
Auxiliary output
16 A
PowerAssist
on
5.2 Explanation of settings
Settings that are not self-explanatory are described briefly below. For further information, please refer to the help files in the software
configuration programs (see Section 5.3).
Inverter frequency
Output frequency if no AC is present at the input.
Adjustability: 50 Hz; 60 Hz
Input frequency range
Input frequency range accepted by the MultiPlus. The MultiPlus synchronises within this range with the AC input frequency. The output
frequency is then equal to the input frequency.
Adjustability: 45 – 65 Hz; 45 – 55 Hz; 55 – 65 Hz
Input voltage range
Voltage range accepted by the MultiPlus. The MultiPlus synchronises within this range with the AC input voltage. The output voltage is
then equal to the input voltage.
Adjustability:
Lower limit: 180 – 230 V
Upper limit: 230 – 270 V
Note
: the standard lower limit setting of 180V is intended for connection to a weak mains supply, or to a generator with unstable AC
output. This setting may result in a system shut down when connected to a ‘brushless, self excited, externally voltage regulated,
synchronous AC generator’ (synchronous AVR generator). Most generators rated at 10kVA or more are synchronous AVR generators.
The shut down is initiated when the generator is stopped and revs down while the AVR simultaneously ‘tries’ to keep the output voltage
of the generator at 230 V.
The solution is to increase the lower limit setting to 210VAC (the output of AVR generators is generally very stable), or to disconnect the
Multi(s) from the generator when a generator stop signal is given (with help of an AC contactor installed in series with the generator).
Содержание MultiPlus Compact 12/1200/50-16
Страница 2: ......
Страница 29: ......
Страница 30: ...www victronenergy com Appendix A overview connections ...
Страница 31: ...Appendix A overview connections ...
Страница 33: ...Appendix B installation information ...
Страница 35: ...APPENDIX C parallel connection ...
Страница 36: ...www victronenergy com APPENDIX D three phase connection ...
Страница 39: ......
Страница 40: ...www victronenergy com ...
Страница 42: ...Manual Handleiding Manuel Anleitung Manual MultiPlus Compact 12 2000 80 30 230V 24 2000 50 30 230V ...
Страница 43: ......
Страница 70: ...APPENDIX A Connection overview ...
Страница 72: ...APPENDIX B Installation information ...
Страница 74: ...APPENDIX C Parallel connection APPENDIX D Three phase connection ...
Страница 77: ...www victronenergy com 255m 125m 520m 95mm ...
Страница 78: ......
Страница 79: ......
Страница 82: ......
Страница 106: ...24 ...
Страница 120: ...APPENDIX G Dimensions ANNEXE G Dimensions ANHANG G Maße APÉNDICE G Dimensiones APPENDIX G Dimensioner ...
Страница 121: ......
Страница 122: ......
Страница 123: ......