APPENDIX E: Charge characteristic
Charge current
0%
20%
40%
60%
80%
100%
120%
Time
Amps
Charge voltage
10
11
12
13
14
15
16
Time
Volts
4-stage charging:
Bulk
Entered when charger is started. Constant current is applied until nominal battery voltage is reached, depending on temperature and input voltage, after
which constant power is applied up to the point where excessive gassing is starting (14.4V resp. 28.8V, temperature compensated).
Battery Safe
The applied voltage to the battery is raised gradually until the set Absorption voltage is reached. The Battery Safe Mode is part of the calculated
absorption time.
Absorption
The absorption period is dependent on the bulk period. The maximum absorption time is the set Maximum Absorption time.
Float
Float voltage is applied to keep the battery fully charged
Storage
After one day of float charge the output voltage is reduced to storage level. This is 13,2V resp. 26,4V (for 12V and 24V charger). This will limit water loss
to a minimum when the battery is stored for the winter season.
After an adjustable time (default = 7 days) the charger will enter Repeated Absorption-mode for
an adjustable time (default = one hour) to ’refresh’ the
battery.
Содержание MultiPlus 3000
Страница 1: ...MultiPlus with firmware xxxx400 or higher 12 3000 120 50 120V 24 3000 70 50 120V Manual EN Appendix ...
Страница 2: ......
Страница 26: ......
Страница 27: ...EN Appendix APPENDIX A Overview connections ...
Страница 29: ...EN Appendix APPENDIX B Block diagram See table in Chapter 4 2 Recommended DC fuse ...
Страница 34: ...APPENDIX G Dimensions ...
Страница 35: ...EN Appendix ...
Страница 36: ......
Страница 37: ......