22
All of the conditions below must be met!:
1.
The device is in error! (No AC output)
2.
Inverter LED flashes (in opposition to any flashing of the Bulk, Absorption or Float LED)
3.
At least one of the LEDs Bulk, Absorption and Float is on or flashing
Bulk LED off
Bulk LED flashes
Bulk LED on
Absorption LED
Absorption LED
Absorption LED
off
flashing
On
off
flashing
on
off
flashing
on
F
lo
a
t L
E
D
off
0
3
6
F
lo
a
t L
E
D
off
9
12
15
F
lo
a
t L
E
D
off
18
21
24
flashing
1
4
7
flashing
10
13
16
flashing
19
22
25
on
2
5
8
on
11
14
17
on
20
23
26
Bulk LED
Absorption LED
Float LED
Code
Meaning:
Cause/solution:
1
Device is switched off because one of
the other phases in the system has
switched off.
Check the failing phase.
3
Not all, or more than, the expected
devices were found in the system.
The system is not properly configured. Reconfigure the system.
Communication cable error. Check the cables and switch all equipment off,
and then on again.
4
No other device whatsoever detected.
Check the communication cables.
5
Overvoltage on AC-out.
Check the AC cables.
10
System time synchronisation problem
occurred.
Should not occur in correctly installed equipment. Check the communication
cables.
14
Device cannot transmit data.
Check the communication cables (there may be a short circuit).
17
One of the devices has assumed
‘master’ status because the original
master failed.
Check the failing unit. Check the communication cables.
18
Overvoltage has occurred.
Check AC cables.
22
This device cannot function as ‘slave’.
This device is an obsolete and unsuitable model. It should be replaced.
24
Switch-over system protection initiated.
Should not occur in correctly installed equipment. Switch all equipment off,
and then on again. If the problem recurs, check the installation.
25
Firmware incompatibility. The firmware
of one the connected devices is not
sufficiently up to date to operate in
conjunction with this device.
1) Switch all equipment off.
2) Switch the device returning this error message on.
3) Switch on all other devices one by one until the error message reoccurs.
4) Update the firmware in the last device that was switched on.
26
Internal error.
Should not occur. Switch all equipment off, and then on again. Contact
Victron Energy if the problem persists.
Содержание MultiPlus 3000
Страница 1: ...MultiPlus with firmware xxxx400 or higher 12 3000 120 50 120V 24 3000 70 50 120V Manual EN Appendix ...
Страница 2: ......
Страница 26: ......
Страница 27: ...EN Appendix APPENDIX A Overview connections ...
Страница 29: ...EN Appendix APPENDIX B Block diagram See table in Chapter 4 2 Recommended DC fuse ...
Страница 34: ...APPENDIX G Dimensions ...
Страница 35: ...EN Appendix ...
Страница 36: ......
Страница 37: ......