background image

7. Trouble Shooting Table

Proceed as follows for quick detection of common faults.

DC loads must be disconnected from the batteries and the AC loads must be disconnected from the inverter before the inverter
and/or battery charger is tested.

Consult your Victron Energy dealer if the fault cannot be resolved.

Problem

Cause

Solution

The inverter fails to operate
when switched on

The battery voltage is too high or too
low

Ensure that the battery voltage is within the
correct value.

The inverter fails to operate

Processor in no function-mode

Disconnect mains voltage. Switch front switch
off, wait 4 seconds.

Switch front switch on.

The alarm LED flashes

Pre-alarm alt. 1. The DC input voltage
is low

Charge the battery or check the battery
connections.

The alarm LED flashes

Pre-alarm alt. 2. The ambient
temperature is too high

Place the inverter in a cool and well-ventilated
room, or reduce the load.

The alarm LED flashes

Pre-alarm alt. 3. The load on the
inverter is higher than the nominal load

Reduce the load.

The alarm LED flashes

Pre-alarm alt. 4. Voltage ripple on the
DC input exceeds 1.25Vrms

Check the battery cables and terminals.

Check the battery capacity; increase if
necessary.

The alarm LED flashes
intermittantly

Pre-alarm alt. 5. Low battery voltage
and excessive load

Charge the batteries, reduce the load or install
batteries with a higher capacity. Use shorter
and/or thicker battery cables.

The alarm LED is on

The inverter did cut out following a pre-
alarm

Check the table for the appropriate course of
action.

The charger is not
functioning

The AC input voltage or frequency is
out of range

Ensure that the input voltage is between
185Vac and 265Vac, and that the frequency
matches the setting.

The battery is not being
charged fully

Incorrect charging current

Set the charging current at between 0.1 and
0.2x battery capacity.

A defective battery connection

Check the battery terminals.

The absorption voltage has been set to
an incorrect value

Adjust the absorption voltage to the correct
value.

The float voltage has been set to an
incorrect value

Adjust the float voltage to the correct value.

The internal DC fuse is defective

Inverter is damaged.

The battery is overcharged

The absorption voltage has been set to
an incorrect value

Adjust the absorption voltage to the correct
value.

The float voltage has been set to an
incorrect value

Adjust the float voltage to the correct value.

A defective battery

Replace the battery.

The battery is too small

Reduce the charging current or use a battery
with a higher capacity.

The battery is too hot

Connect a temperature sensor.

Battery charge current drops
to 0 when the absorption
voltage is reached

Alt. 1: Battery overtemperature (>
50°C)

• Allow battery to cool down
• Place battery in a cool environment
• Check for shorted cells

MultiPlus 2kVA 120V

Page 15

Trouble Shooting Table

Содержание MultiPlus 2kVA 120V

Страница 1: ...MultiPlus 2kVA 120V rev 00 2021 ENGLISH ...

Страница 2: ... C 7 4 4 6 Three phase operation see appendix D 8 5 Configuration 9 5 1 Standard settings ready for use 9 5 2 Explanation of settings 9 5 3 Configuration of the MultiPlus 11 5 3 1 VE Bus Quick Configure Setup 12 5 3 2 VE Bus System Configurator 12 5 4 Configuration with DIP switches 12 5 4 1 DIP switch 1 to 3 12 5 4 2 Exemplary settings 12 6 Maintenance 14 7 Trouble Shooting Table 15 8 Technical D...

Страница 3: ...nce by a person responsible for their safety Children should be supervised to ensure that they do not play with the appliance Do not lift heavy loads without assistance Installation Read the installation instructions in the installation manual before installing the equipment This is a Safety Class I product supplied with a protective grounding terminal Uninterruptible protective grounding must be ...

Страница 4: ...lay can be programmed for all kinds of other applications however for example as a starter relay for a generator 2 2 Battery charger Adaptive 4 stage charging characteristics bulk absorption float storage The microprocessor driven adaptive battery management system can be adjusted for various types of batteries The adaptive function automatically adapts the charging process to battery use The righ...

Страница 5: ... code compliance by selecting the grid code country setting with the VEConfigure tool Once set a password will be required to disable grid code compliance or change grid code related parameters If the local grid code is not supported by the MultiPlus an external certified interface device should be used to connect the MultiPlus to the grid Special note for Australian customers IEC62109 1 certifica...

Страница 6: ...h is switched to charger only This prevents the inverter from being switched on if the mains voltage is lost thus preventing the batteries from running flat 3 2 Remote control Remote control is possible with a switch or with a Multi Control panel The Multi Control panel has a simple rotary knob with which the maximum current of the AC input can be set see PowerControl in Section 2 3 3 LED Indicati...

Страница 7: ...Energy Storage System ESS The AC input voltage is switched through The inverter is switched on and supplies power to the load or excess power to the mains Charger only On Off Charger only switch Charger only The AC input voltage is switched through and the charger operates in bulk or absorption mode On Off Charger only switch Charger only The AC input is switched through and the charger operates i...

Страница 8: ...2000 25 Recommended battery capacity Ah 350 1000 200 500 100 250 Recommended DC fuse 300A 200A 100A Recommended cross section mm2 per and connection terminal 0 5 m 70mm 2 35 mm2 25 mm2 5 10 m 95mm2 70 mm2 50mm2 Remark Internal resistance is the important factor when working with low capacity batteries Please consult your supplier or the relevant sections of our book Energy Unlimited downloadable f...

Страница 9: ... can be connected directly to the terminal block AC out From left to right L neutral PE earth and N phase With its PowerAssist feature the MultiPlus can add up to 2kVA that is 2000 120 16A to the output during periods of peak power requirement Together with a maximum input current of 50A this means that the output can supply up to 50 16 66 A An earth leakage circuit breaker and a fuse or circuit b...

Страница 10: ...nder above and beside the units A battery temperature sensor need only be connected to one unit in the system If the temperature of several batteries is to be measured you can also connect the sensors of other MultiPlus units in the system with a maximum of one sensor per MultiPlus Temperature compensation during battery charging responds to the sensor indicating the highest temperature Only one r...

Страница 11: ...with BatterySafe mode Charge current 100 of the maximum charge current Battery type Victron Gel Deep Discharge also suitable for Victron AGM Deep Discharge Automatic equalisation charging off Absorption voltage 14 4 28 8 57 6V Absorption time up to 8 hours depending on bulk time Float voltage 13 8 27 6 55 2V Storage voltage 13 2 26 4 52 8V not adjustable Repeated absorption time 1 hour Absorption ...

Страница 12: ...rch mode the AES mode can also be chosen with help of VEConfigure only If this setting is turned on the power consumption in no load operation and with low loads is decreased by approx 20 by slightly narrowing the sinusoidal voltage Ground relay see appendix B With this relay H the neutral conductor of the AC output is grounded to the chassis when the back feed safety relay is open This ensures th...

Страница 13: ... connected to a generator with a synchronous AVR regulated alternator The UPS mode may have to be set to off if the MultiPlus is connected to a generator with a synchronous capacitor regulated alternator or an asynchronous alternator Dynamic current limiter Intended for generators the AC voltage being generated by means of a static inverter so called inverter generators In these generators rpm is ...

Страница 14: ... one time 5 4 1 DIP switch 1 to 3 These DIP switches can be used to set Battery charge voltage and Absorption time Search mode Ds1 ds2 Setting the charge algorithm For more system settings use VEConfigure Ds1 ds2 Absorption voltage Float voltage Storage Voltage Absorption Time hours Suitable for Ds1 off Ds2 off default 14 4 28 8 57 6 13 8 27 6 55 2 13 2 26 4 52 8 8 Gel Victron Deep Discharge Gel E...

Страница 15: ...e off 3 Store setting off on off Example 2 1 2 Gel Victron Long Life Li ion LiFePO4 3 Search mode off 3 Store setting off on off Example 3 1 2 Tubular plate 15V 3 Search mode off 3 Store setting off on off Store the settings by toggling DIP switch 3 one time The LEDs charger and alarm will flash to indicate acceptance of the settings MultiPlus 2kVA 120V Page 13 Configuration ...

Страница 16: ...ance The MultiPlus does not require specific maintenance It will suffice to check all connections once a year Avoid moisture and oil soot vapours and keep the device clean MultiPlus 2kVA 120V Page 14 Maintenance ...

Страница 17: ...or install batteries with a higher capacity Use shorter and or thicker battery cables The alarm LED is on The inverter did cut out following a pre alarm Check the table for the appropriate course of action The charger is not functioning The AC input voltage or frequency is out of range Ensure that the input voltage is between 185Vac and 265Vac and that the frequency matches the setting The battery...

Страница 18: ...temperature sensor from the MultiPlus Reset the MultiPlus by switching it off then wait for 4 seconds and switch it on again If the MultiPlus now charges normally the battery temperature sensor is faulty and needs to be replaced MultiPlus 2kVA 120V Page 16 Trouble Shooting Table ...

Страница 19: ...at 13 8 27 6 55 2V Storage mode 13 2 26 4 52 8V Charge current house battery 4 80 50 25A Charge current starter battery 1 A 12V and 24V models only Battery temperature sensor Yes GENERAL Programmable relay 5 Yes Protection 2 a g Common Characteristics Operating temp range 40 to 65 C fan assisted cooling Humidity non condensing max 95 ENCLOSURE Common Characteristics Material Colour Steel ABS blue ...

Страница 20: ... d Battery voltage too low e Temperature too high f 230VAC on inverter output g Input voltage ripple too high 3 Non linear load crest factor 3 1 4 At 25 C ambient 5 Programmable relay which can be set for general alarm DC under voltage or generator start stop signal function AC rating 230V 4A DC rating 4A up to 35VDC 1A up to 60VDC MultiPlus 2kVA 120V Page 18 Technical Data ...

Страница 21: ...charger only switch C VE BUS Communications port D Temperature sensor E Alarm contact F Batterie Minus G Starter battery plus H Remote control I Mains IN J Mains converter OUT K Battery plus L Earth connection 9 2 Appendix B installation information MultiPlus 2kVA 120V Page 19 APPENDIX ...

Страница 22: ...chassis G Backfeed safety relay H Ground relay closed when backfeed is open J Bidirectional converter K Chassis on input output ground terminals should be permanently connected to ground 9 3 Appendix C parallel connection MultiPlus 2kVA 120V Page 20 APPENDIX ...

Страница 23: ...9 4 Appendix D three phase connection 9 5 Appendix E charge algorithm MultiPlus 2kVA 120V Page 21 APPENDIX ...

Страница 24: ...n time is equal to 20x bulk time or the set maximum absorption time whichever comes first Float Float voltage is applied to keep the battery fully charged and to protect it against self discharge Storage After one day of Float charge the charger switches to storage This is 13 2V resp 26 4V for 12V and 24V charger This will limit water loss to a minimum After an adjustable time default 7 days the c...

Страница 25: ...MultiPlus 2kVA 120V Page 23 APPENDIX ...

Отзывы: