Location
The Centaur Charger must be installed in a dry, well-ventilated
area.
Too high an ambient temperature has the consequence of lower
output, shorter life or a complete shutdown of the Centaur
Charger.
The Centaur Charger is suitable for floor and wall mounting.
However, for optimum cooling, a vertical position is recommended.
The cables between the Centaur Charger and the battery must be
kept as short as possible to minimize cable losses. Input/output
connections refer to Figure 1.
Required tools and cables
•
M6 Socket driver.
•
Crosshead screwdriver no. 2 Phillips.
•
Battery cables: minimum cable cross-section
Model
Length 0 - 6 m
12/20
24/16
10 mm²
AWG 7
12/30
12/40
24/30
24/40
16 mm²
AWG 5
12/50
12/60
24/60
25 mm²
AWG 3
12/80
12/100
24/80
24/100
35 mm²
AWG 2
12/200
50 mm²
AWG 0