11
4. Specifications
Centaur Charger
12/20
12/30
24/16
12/40
12/60
24/30
12/80
24/40
12/100
24/60
12/160
24/80
12/200
24/100
Common characteristics
Input voltage: 90 – 265 V Input frequency: 45 – 65 Hz Power factor: 1
Charge voltage ‘absorption’
(V DC)
14,3 / 28,5
(1)
Charge voltage ‘float’
(V DC)
13,5 / 27,0
(1)
Output banks
3
Charge current (A)
(2)
20 30/
16 40 60/
30
80/
40
100/ 60
160/ 80
200/ 100
Total output ammeter
Yes
Charge characteristic
IUoU (Three stage charging)
Recommended battery
capacity (Ah)
80 -
200
120-
300
45-
150
160-
400
240-
600
120-
300
320-
800
160-
400
400-
1000
240-
600
640-
1600
320-
800
800-
2000
400-
1000
Temperature sensor
Internal, - 2mV / °C (- 1mV / °F) per cell
Forced cooling
Yes, temperature and current controlled fan
Protection
Output short circuit, over temperature
Operating temp. range
- 20 to 60°C (0 - 140°F)
Ignition protected
Yes
Humidity (non condensing)
max 95%
ENCLOSURE
Material & Colour
aluminium (blue RAL 5012)
Battery-connection
M6
studs
M6
studs
M8
studs
M8
studs
M8
studs
M8
studs
M8
studs
M8
studs
AC-connection
screw-clamp 4 mm² (AWG 6)
Protection category
IP 21
Weight kg (lbs)
3,8 (8.4)
3,8
(8.4)
5 (11)
5 (11)
12 (26)
12 (26)
16 (35)
16 (35)
Dimensions
hxwxd in mm
(hxwxd in inches)
355x215
x110
(
14.0x8.5
x4.3)
355x215
x110
(
14.0x8.5
x4.3)
426x239
x135
(
16.8x9.4
x5.3)
426x239
x135
(
16.8x9.4
x5.3)
505x255
x130
(
19.9x10.0
x5.2)
505x255
x130
(
19.9x10.0
x5.2)
505x255
x230
(
19.9x10.0
x9.1)
505x255
x230
(
19.9x10.0
x9.1)
STANDARDS
Safety
EN 60335-2-29, UL 1236
Emission
EN 55014, EN 61000-3-2, EN 61000-3-3
Immunity
EN 55014-2
1)Standard setting.
Optimum charge/float voltages for Flooded Lead-acid, Gel-Cell or AGM batteries selectable by dip switch.
2) Up to 40 °C (100 °F) ambient.
Output will reduce to approximately 80 % of nominal at 50 °C (120 °F) and 60 % of nominal at 60 °C (140°F).