PROBLEM

POSSIBLE CAUSE

REMEDY

1.  Condensing unit fails to start - no

hum.

2.  Condensing unit fails to start -

hums, but trips on overload 

protector.

3.  Condensing unit starts, but fails

to switch off of “start” winding.

4.  Condensing unit starts and runs,

but short cycles on overload

protector.

5.  Condensing unit runs but short

cycles on...

6.  Condensing unit operates for

prolonged periods or

continuously.

1.  Line disconnect switch open.

2.  Fuse removed or blown.

3.  Overload protector tripped.

4.  Control stuck in open position.

5.  Wiring improper or loose.

1.  Improperly wired.

2.  Low voltage to unit.

3.  Starting capacitor defective.

4.  Relay failing to close.

5.  Compressor motor has a winding

open or shorted.

6.  Internal mechanical trouble in 

compressor.

1.  Improperly wired.

2.  Low voltage to unit.

3.  Relay failing to open.

4.  Run capacitor defective.

5.  Excessively high discharge

pressure.

6.  Compressor motor has a winding

open or shorted.

7.  Internal mechanical trouble in 

compressor.

1.  Additional current passing through

overload protector.

2.  Low voltage to unit (or

unbalanced if three phase.)

3.  Overload protector defective.

4.  Run capacitor defective.

5.  Excessive discharge pressure.

6.  Suction pressure too high.

7.  Compressor too hot - return gas.

8.  Compressor motor has a winding 

shorted.

1.  Overload protector.

2.  Thermostat.

3.  High pressure cut-out due to:

a. Insufficient air or water supply.

b. Overcharge.

c. Air in system.

4.  Low pressure cut-out due to:

a. Liquid line solenoid leaking.
b. Compressor valve leak.

c. Undercharge.

d. Restriction in expansion

device.

1.  Shortage of refrigerant.

2.  Control contacts stuck or frozen 

closed.

3.  Excessive heat load placed into 

cabinet.

4.  Prolonged or too frequent door

openings. 

5.  Evaporator coil iced.

6.  Restriction in refrigeration

system.

7.  Dirty condenser.

8.  Filter dirty.

1.  Close start or disconnect switch.

2.  Replace fuse.

3.  Determine reason and

correct/replace control.

4.  Repair or replace control.

5.  Check wiring against diagram.

1.  Check wiring against diagram.

2.  Determine reason and correct.
3.  Determine reason and replace.

4.  Determine reason and

correct/replace if necessary.

5.  Replace compressor.

6.  Replace compressor.

1.  Check wiring against diagram.

2.  Determine reason and correct.

3.  Determine reason and

correct/replace if necessary.

4.  Determine reason and replace.

5.  Check discharge shut-off valve,

possible overcharge, or

insufficient cooling on condenser.

6.  Replace compressor.

7.  Replace compressor.

1.  Check wiring diagram.  Check for

added fan motors, pumps, etc. con-

nected to wrong side of protector.

2.  Determine reason and correct.

3.  Check current , replace protector.

4.  Determine reason and replace.

5.  Check ventilation, restrictions in

cooling medium, restrictions in 

refrigeration system.

6.  For salad models, temperature

control differential set to close-

increase differential.

7.  Check refrigerant charge (fix leak)

add if necessary.

8.  Replace compressor.

1.  See (4) above.

2.  Differential set too close - widen.

3. 

a. Check air or water supply to 

condenser-correct.

b. Reduce refrigerant charge.
c. Purge.

4.

a. Replace.
b. Replace.

c. Fix leak, add refrigerant.
d. Replace device.

1.  Fix leak, add charge.

2.  Clean contacts or replace control.

3.  Allow unit sufficient time for

removal of latent heat.

4.  Plan or organize schedule to 

correct condition.

5.  Defrost.

6.  Determine location and remove.

7.  Clean condenser.

8.  Clean or replace.

TROUBLESHOOTING & SERVICING REFRIGERATION SYSTEM

Содержание GFS- 3D- S7

Страница 1: ...00 Fax 856 428 7299 Website www victory refrig com E Mail parts victory refrig com order entry victory refrig com service victory refrig com For Models GFS 1D S7 GFS 2D S7 GFS 3D S7 GRS 1D S7 GRS 2D S...

Страница 2: ...6 428 4200 IMPORTANT INFORMATION PLEASE READ Please read these instructions carefully before installing or using If recommended procedures are not followed warranty claims will be denied Your Warranty...

Страница 3: ...result from the use or misuse by Buyer its employees or others of the equipment supplied hereunder and Buyer s sole and exclusive remedy against Seller for any breach of the foregoing warranty or othe...

Страница 4: ...freezer in an unheated room or where the room temperature may hover below 55 F IMPORTANT VENTILATION NOTE 1 Do not remove the rubber bumper spacer from the rear of the cabinet The bumper guarantees su...

Страница 5: ...r Maintenance Cleaning is recommended at least once every three 3 months 1 Disconnect the electrical service cord from receptacle or trip circuit breaker 2 Use a vacuum cleaner with proper brush attac...

Страница 6: ...or frozen closed 3 Excessive heat load placed into cabinet 4 Prolonged or too frequent door openings 5 Evaporator coil iced 6 Restriction in refrigeration system 7 Dirty condenser 8 Filter dirty 1 Cl...

Страница 7: ...nt or is oversized 1 Restriction in dehydrator or strainer 2 Liquid shut off king valve partially closed 1 Loose parts or mounting 2 Tubing rattle 3 Bent fan blade causing vibration 4 Fan motor bearin...

Отзывы: