IMPORTANT INSTALLATION INFORMATION

 

WARNING

•  Read and understand all instructions 

before attempting to install, remove, 
adjust, or maintain any Victaulic piping 
products.

•  Depressurize and drain the piping 

system before attempting to install, 
remove, adjust, or maintain any 
Victaulic products.

•  Wear hardhat, safety glasses, and foot 

protection.

Failure to follow these instructions could 
result in serious personal injury, property 
damage, and/or product damage.

 CAUTION

•  To ensure maximum gasket life, make sure the strainer is 

installed with a Victaulic-supplied gasket grade that is suitable 
for the intended service.

•  Strainer baskets must be cleaned out prior to obtaining 10-psi/ 

0.7-Bar/69-kPa pressure differential across the basket.

Failure to follow these instructions could cause joint leakage and 
property damage.

The information contained in this instruction sheet must be referenced 
to ensure proper installation of Series 732H FireLock Wye-Type Vic-
Strainers. 

NOTE:

 Maximum service life is dependent upon proper 

gasket selection and installation. Refer to Victaulic publication 05.01, 
“Gasket Selection Guide,” for details.

ASSEMBLY CLEARANCE

• 

Select a location for the Vic-Strainer that accommodates the minimum clearance requirements for removing the strainer basket (refer to the table 
below). 

NOTE:

 Series 732H FireLock Vic-Strainers are shipped fully assembled.

Minimum Clearance Requirements for Removal of Strainer Basket

Size

“C” Strainer Basket Minimum Clearance 

Dimensions inches/mm

Nominal Size 

inches or mm

Actual Pipe Outside 

Diameter inches/mm

2

2.375

8.00

60.3

203

21/2

2.875

9.00

73.0

229

76.1 mm

3.000

9.00

76.1

229

3

3.500

10.00

88.9

254

4

4.500

12.00

114.3

305

C

Series 732H FireLock Wye-Type Vic-Strainers

Typical 2 – 4-inch/60.3 – 114.3-mm Sizes

INSTALLATION OF THE VIC-STRAINER

1. 

The outside surface of the pipe (from the pipe end to the groove) 
must be smooth and free from indentations, projections (including 
weld seams), and roll marks to ensure a leak-tight seal. All oil, 
grease, loose paint, and dirt must be removed prior to installation.

FLOW

FLOW

2.  Align the Vic-Strainer to the piping system so that the flow into 

and out of the strainer matches the directional arrows cast into 
the strainer body. Install the Vic-Strainer by using two Victaulic 
couplings that are suitable for the intended service. Always refer 
to the Victaulic Field Installation Handbook (I-100) for complete 
coupling installation requirements.

I-732H_1