46.03
16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved.
ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT.
FL-SA/DS, V5621
FL-SA/GAP, V5623
FL-SA/BB, V8122
FL-SA/BB, V8123
FL-SA/BB, V8124
1.0 PRODUCT DESCRIPTION
SPECIFIC APPLICATION ATTIC SPRINKLERS
SIN
V5621
V5623
V8122
V8123
V8124
ORIENTATION
UPRIGHT
UPRIGHT
UPRIGHT
UPRIGHT
UPRIGHT
K-FACTOR1
5.6 Imp./8.1 S.I.
5.6 Imp./8.1 S.I.
8.0 Imp./11.5 S.I.
8.0 Imp./11.5 S.I.
8.0 Imp./11.5 S.I.
CONNECTION
1/2” NPT/15mm BSPT
1/2” NPT/15mm BSPT
3/4" NPT/ 20mm BSPT
3/4" NPT/ 20mm BSPT
3/4" NPT/ 20mm BSPT
MAX. WORKING PRESSURE
175 psi (1200 kPa)
175 psi (1200 kPa)
175 psi (1200 kPa)
175 psi (1200 kPa)
175 psi (1200 kPa)
GLOBE RE-DESIGNATION
GL5621
GL5623
GL8122
GL8123
GL8124
AVAILABLE WRENCHES
SPRINKLER
V56 Open End
V81 Open End
Upright
■
■
Factory Hydrostatic Test:
100% @ 500 psi/3447 kPa/34 bar
Min. Operating Pressure:
UL: 7 psi/48 kPa/.5 bar
Temperature Rating:
See tables in section 2.0
1
For K-Factor when pressure is measured in bar, multiply S.I. units by 10.0.
2.0 CERTIFICATION/LISTINGS
Sprinkler Model
SIN
Nominal K Factor
Listing Agency/
Approved
Temperature Ratings
Area of Use
Maximum
Roof Span
Roof Pitch
Imperial
ft
BB46
V8122
8.0
cULus 200°F/93°C
RIDGE/GABLE
60
4:12 to less than 7:12
BB46/GAP
V8122/V5623
8.0/5.6
cULus 200°F/93°C
RIDGE/GABLE and
GAP at EAVE
84
4:12 to less than 7:12
BB79
V8123
8.0
cULus 200°F/93°C
RIDGE/GABLE
60
7:12 to less than 10:12
BB79/GAP
V8123/V5623
8.0/5.6
cULus 200°F/93°C
RIDGE/GABLE and
GAP at EAVE
84
7:12 to less than 10:12
BB1012
V8124
8.0
cULus 200°F/93°C
RIDGE/GABLE
60
10:12 to 12:12
BB1012/GAP
V8124/V5623
8.0/5.6
cULus 200°F/93°C
RIDGE/GABLE and
GAP at EAVE
84
10:12 to 12:12
GAP
V5623
5.6
cULus 200°F/93°C
EAVE/HIP
N/A
SEE LAYOUT CRITERIA
DS
V5621
5.6
cULus 200°F/93°C
HIP/SINGLE SLOPE
N/A
SEE LAYOUT CRITERIA
NOTES
• Listings and approval as of printing.
• Listed to be utilized per NFPA 13 in conformance with the New Technology and Equivalency Sections.
Victaulic
®
FireLock
™
Series FL-SA/GAP and FL-SA/BB
Specific Application Back-To-Back Attic Protection Scheme,
Quick Response Upright, K5.6 (8.0), K8.0 (11.5)
46.03
1