Victaulic 746-LPA Series Скачать руководство пользователя страница 2

AIR SUPPLY REQUIREMENTS

Systems with air pressure higher than 18 psi/124 kPa require the 
a ddition of a Series 746-LPA Dry Accelerator.

COMPRESSOR REQUIREMENTS AND SETTINGS FOR SYSTEMS 
INSTALLED WITH SERIES 746-LPA DRY ACCELERATORS

0

2

4

6

8

10

12

System Capacity (in gallons)

Requir

ed F

lo

w

 R

a

te

 (

C

F

M

)

550

300

50

800

1050

1300

1550

1800

20 psi/138 kPa
13 psi/90 kPa

In the event a compressor becomes inoperative, a properly sized tank-
mounted air compressor provides the greatest protection for systems 
installed with a Series 746-LPA Dry Accelerator. In this situation, air can 
be supplied continuously to the sprinkler system for an extended time 
period. 

NOTE:

 The Series 757 Regulated AMTA should be used with a 

tank-mounted air compressor to supply air to a system when the Series 
746-LPA Dry Accelerator is used. The use of an air regulator with a 
base or riser-mounted compressor could cause short cycling, resulting 
in premature wear of the compressor.

Set the air regulator of the Series 757 Regulated Air Maintenance Trim 
Assembly (AMTA) to a minimum of 13 psi/90 kPa.

The air regulator of the Series 757 Regulated AMTA is a relief-type 
design. Any pressure in the system that is above the set point of the air 
regulator will be released. Therefore, charging the air regulator above 
the set point could cause premature operation of a system installed with 
a Series 746-LPA Dry Accelerator.

THE SERIES 757P AIR MAINTENANCE TRIM ASSEMBLY WITH 
PRESSURE SWITCH MUST NOT BE USED ON A SYSTEM 
INSTALLED WITH A SERIES 746-LPA DRY ACCELERATOR.

INSTALLATION

For proper operation and approval, the valve and any accessories must 
be installed in accordance with the specific trim diagrams included with 
the shipment.

 CAUTION

Make sure no foreign material gets into the pipe nipples and 
openings in the accelerator.

If using any material other than Teflon* tape, use extra 
 caution so that no material gets into the trim.

Failure to follow these instructions could cause improper valve 
operation, resulting in personal injury and/or property damage.

1. 

Apply a small amount of pipe joint compound or Teflon* tape to 
the external threads of all threaded pipe connections. DO NOT get 
any tape, compound, or other foreign material into the pipe nipples 
and openings in the accelerator.

2. 

Assemble the Series 746-LPA Dry Accelerator per the drawing 
provided.

3. 

Install the Series 746-LPA Dry Accelerator into the trim of the 
actuator in the location designated on the applicable trim draw-
ing. Make sure the end of the Series 746-LPA with the vent seal 
 “button” is facing toward the trim of the actuator.

PLACING THE SYSTEM IN SERVICE

When the system is ready to be placed in service, refer to the instal-
lation, maintenance, and testing manual for the applicable valve for 
detailed setup instructions. 

*TEFLON IS A REGISTERED TRADEMARK OF THE DUPONT COMPANY.

I-746.LPA_2

Series 746-LPA

INSTRUCTIONS FOR INSTALLING AND REPAIRING SERIES 746-LPA DRY ACCELERATORS

I-746.LPA

INSTALLATION AND REPAIR KIT INSTRUCTIONS

www.victaulic.com

VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2006 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

REV_A

Содержание 746-LPA Series

Страница 1: ...essure from the actuator resulting in valve operation BILL OF MATERIALS 1 Opening Air Chamber 8 Seal Support 2 Piston 9 Button Head Cap Screw 3 Restrictor 10 Closing Chamber Seal 4 Diaphragm 11 Washer...

Страница 2: ...OT BE USED ON A SYSTEM INSTALLED WITH A SERIES 746 LPA DRY ACCELERATOR INSTALLATION For proper operation and approval the valve and any accessories must be installed in accordance with the specific tr...

Страница 3: ...false trip resulting in property damage CONTENTS OF REPAIR KIT Item Qty Description 1 1 Diaphragm 2 1 Check Valve with O Ring 3 1 Restrictor 4 2 O Ring 1 Close the isolation ball valve of the Series 7...

Страница 4: ...the cap screw that retains the piston Keep this cap screw for re installation 9 Remove the piston the two o rings the restrictor and the diaphragm Keep the piston for re assembly Discard the restricto...

Страница 5: ...around the restrictor 14 Install a NEW o ring provided with the kit into the recess in the piston that IS NOT counterbored as shown above 15 Align the recesses in the piston with the holes in the dia...

Страница 6: ...ully tighten the four cap screws 21 Re apply a small amount of pipe joint compound or Teflon tape to the nipple above the isolation ball valve DO NOT get any tape compound or other foreign material in...

Страница 7: ...onfirm system integrity If there is degradation in system air pressure find and correct all leaks NOTE NFPA requires less than 2 psi 14 kPa leakage in 24 hours 26 Notify the authority having jurisdict...

Страница 8: ...ly cannot get pressure on the upper gauge and the button pops up immediately when pressure is introduced The Series 746 LPA Dry Accelerator is installed upside down Remove the Series 746 LPA Dry Accel...