The recommended process for Balancing the system is:
1.  On page “1/2 Balancing (PI)”, check the Minimum, Maximum Cooling, Maximum Heating and Reheat airflow setpoints are 

correctly configured for the zone.

2.  Check airflow sensor is correctly zeroed:

a.  On page “2/2 Balancing (PI)”, set Damper Override to Close.

b.  Wait for measured “Airflow level” to stabilize and confirm the value is less than the desired Minimum Airflow. If  not, confirm 

damper is closed and auto-zero the airflow sensor. Refer to the flow sensor Installation Guide for more information on 
zeroing.

3.  Before setting the Minimum and Maximum Cooling airflow, make sure that when fully open, the airflow is at least 40-60 CFM 

higher than the planned Maximum Cooling airflow. Otherwise, the control will be erratic. 

NOTICE

MINIMUM AND MAXIMUM COOLING AIRFLOW

When damper is fully open, the airflow must be at least 40-60 CFM higher than the planned Maximum Cooling airflow.

Failure to follow these instructions can result in erratic airflow control depending on the HVAC design.

4.  Calibrate sensor at Minimum airflow:

a.  On page “2/2 Balancing (PI)”, set the Damper Override to Minimum Flow. The displayed Airflow Setpoint will use the value 

of  Minimum Airflow.

b.  Wait for the Room Controller measured “Airflow level” to stabilize.

c.  Take a reading of  the actual airflow using a calibrated Balometer.

d.  Enter the actual airflow as the “Balometer” value on “2/2 Balancing (PI)”. The Room Controller will calculate and display a 

new Minimum Flow Offset.

e.  Wait for the measured “Airflow level” to stabilize again. The Airflow level should now match the Airflow setpoint. Repeat if  

necessary.

5.  Calibrate sensor at Maximum Cooling airflow:

a.  On page “2/2 Balancing (PI)”, set the Damper Override to Maximum Cooling. The displayed Airflow Setpoint will use the 

value of  Maximum Cooling Airflow.

b.  Wait for Room Controller measured “Airflow level” to stabilize.

c.  Take reading of  actual airflow using a calibrated Balometer.

d.  Enter the actual airflow as the “Balometer” value on “2/2 Balancing (PI)”.

e.  The Room Controller will calculate and display a new Maximum Flow Offset.

f.  

Wait for the measured “Airflow level” to stabilize again. Airflow level should now match the Airflow setpoint. Repeat if  
necessary.

6.  On page “2/2 Balancing”, revert the Damper Override to None allowing the system to return to normal operation.

Содержание VZ8250

Страница 1: ...VT8000 Room Controllers VZ8250 Installation Guide Variable Air Volume VAV Unit Version 2...

Страница 2: ...RE INDEPENDENT NO FAN 7 4 TYPICAL APPLICATION PRESSURE INDEPENDENT PARALLEL FAN 8 5 TYPICAL APPLICATION PRESSURE DEPENDENT NO FAN 9 6 TERMINAL IDENTIFICATION 10 7 HOME SCREEN DISPLAY 13 8 HOW TO ENTER...

Страница 3: ...ages that follow this symbol to avoid possible injury or death DANGER DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING WARNING indicates a haz...

Страница 4: ...nown to the State of California to cause cancer and birth defects or other reproductive harm For more information go to www P65Warnings ca gov Failure to follow these instructions can result in birth...

Страница 5: ...terior wall Do not install behind a door Do not install in areas with direct heat source Do not install near any air discharge grill Do not install in areas exposed to direct sunlight Ensure Room Cont...

Страница 6: ...nsure the correct side of the base faces up 5 Pull the cables 6in 15cm out from wall 6 Align the base and mark the location of the two mounting holes on the wall 7 Install the anchors in the wall Figu...

Страница 7: ...mmon RH BO8 Aux Heat UO9 Close Damp UO10 Open Valve UO11 0 10V Output UO12 0 10V Output 0 10V Analog Control 7 8 9 10 11 12 1 2 3 4 5 6 BASEBOARD 24V 24V Com 0 10V ANALOG HEATING COIL Com Input RC Inp...

Страница 8: ...19 20 21 22 23 24 BACnet BACnet BACnet REF UI16 UI17 Common UI19 CS UI20 RS C Common UI22 SS UI23 UI24 0 10V Input 0 10V ANALOG HEATING COIL BASEBOARD 24V 24V Com Com Input RC Input RC 0 10V ANALOG A...

Страница 9: ...FAN LO Low voltage TERMINAL BLOCK 13 14 15 16 17 18 19 20 21 22 23 24 BACnet BACnet BACnet REF UI16 UI17 Common UI19 CS UI20 RS C Common UI22 SS UI23 UI24 0 10V Input 1 2 3 4 5 6 BASEBOARD 24V 24V Com...

Страница 10: ...18 or 21 C 24 V Common 24 V Common 10 UO10 0 10V Output Warning Floating duct reheat is not possible when Fan Type is ECM 6 2 AIR FLOW SENSOR PI ONLY Supported air flow sensor parameters Output voltag...

Страница 11: ...18 or 21 C 24 V Common 24 V Common 11 UO11 0 10V Output Floating Actuator Terminal Name Connection 6 18 or 21 C 24 V Common 24 V Common 9 UO9 Close Actuator 11 UO11 Open Actuator Floating actuation ti...

Страница 12: ...se Damper Actuator On Off or PWM Duct Heater Terminal Name Connection Required Settings 6 18 or 21 C 24 V Common 24 V Common Duct Heater Configuration On Off or PWM or Valve NC or Valve NO 12 UO12 24...

Страница 13: ...e Time Occupancy Status System Status Up Arrow Raise Temperature Setpoint Actual Setpoint Room Indoor Temperature Room Indoor Humidity Outdoor Temperature Down Arrow Lower Temperature Setpoint Unoccup...

Страница 14: ...ts For more information on using and configuring the functions of the HMI refer to the VZ8250 User Interface Guide 9 SET UP SCREEN DISPLAY Return to home screen 1 2 Setup Network Configuration Balanci...

Страница 15: ...Pressure Dependent True air flow at various damper percentages will be measured and used to set the appropriate damper percentages for the air flow required for the zone Flow sensor PI only Damper Ca...

Страница 16: ...esign 4 Calibrate sensor at Minimum airflow a On page 2 2 Balancing PI set the Damper Override to Minimum Flow The displayed Airflow Setpoint will use the value of Minimum Airflow b Wait for the Room...

Страница 17: ...ts CFM Min 0 Max 20000 Airflow Setpoint AI350 R Measured calibrated airflow Units CFM Min 0 Max 10000 Minimum Airflow AV250 R W Minimum airflow supplied to the zone Units CFM Min 0 Max 10000 Default 5...

Страница 18: ...l control 1 Min flow Force damper to maintain minimum airflow setpoint 2 Max cool Force damper to maintain maximum cooling airflow setpoint 3 Close Force damper closed 4 Reheat Force damper to maintai...

Страница 19: ...esired position Minimum Maximum Cooling Maximum Heating or Maximum Reheat b Allow time for damper to reach defined position c Take reading of actual air flow using a calibrated Balometer d Compare act...

Страница 20: ...tion AV253 R W Damper position during reheating Units Min 0 Max 100 Damper Override Force damper to selected position during balancing MV172 R W 0 None Default No damper override Damper under normal c...

Страница 21: ...shows Room Controllers installed in ideal locations for two rooms The examination room shows one Room Controller installed adjacent to the door In this area of the room occupant traffic is high and e...

Страница 22: ...ed opposite the door the PIR detection could fall outside the specified detection zone while at the same time most occupant movement would be not be lateral to the PIR thereby not respecting optimal c...

Страница 23: ...l occupancy states transition 8000 with internal and or external motion sensors 8000 Occupancy State Occupied Stand by 8000 with door sensor internal and or external motion sensors 8000 Occupancy Stat...

Страница 24: ...y saving from 10 30 by adjusting temperature set points in unoccupied zones during scheduled periods PIR can maximize your energy saving from 10 30 by adjusting temperature set points in unoccupied zo...

Отзывы: