20 |
028-0324-02_LIT-VZ7656F_B-E01_EN
October 2019
Configuration Parameters
Default Value
SIGNIFICANCE AND ADJUSTMENTS
PswrdSet
Configuration parameters
menu access password
Default value =
0
No password prompted
This parameter sets a password access to prevent
unauthorized access to the configuration menu
parameters. A default value of “0” will not prompt a
password or lock the access to the configuration
menu.
Range is: 0 to 1000
RTC MAC
Zone Controller Controller
network address
Default Value:
4
RTC MAC address must be unique for the entire network.
1 to 255
(Increments: 1 or 10)
For BACnet™ models valid range to use is from 1 to
127.
RTC Baud
RTC Controller
Communication Baud Rate
Default Value: 4 =
Auto
This parameter will set the network’s baud rate.
0 = 9600 KBps
1 = 19200 KBps
2 = 38400 KBps
3 = 76800 KBps
4 = Auto Bauding (Baud Rate will match detected Baud
Rate).
Lockout
Keypad lockout levels
Default value =
0 No lock
0 = No lock
1 = Low level
2 = High level
USER KEY FUNCTIONS
LEVEL
Global
Unocc.
Override
System mode
setting
Schedules
setting
Clock setting
0
1
2
pwr del
Power-up delay
(
Default value =
10 seconds
On initial power up of the Terminal Equipment Controller
each time 24 VAC power supply is removed & re-applied)
here is a delay before any operation is authorized (fan,
cooling or heating). This can be used to sequence start
up multiple units / Terminal Equipment Controller in one
location.
10 to 120 seconds