AA-400 rev.02

1.4.3 Connecting the Earth Ground

The earth ground terminal of the AA-400 must

be connected to the earth ground as follows.

Use a rod at least 5/8 in (16 mm)  in  diameter

at least 10 ft (3 m)  long. The rod must have a

clean metal surface free of paint, enamel or

other nonconducting substances. Drive the rod

at least 10 ft (3 m) into the ground. If the

bedrock is more than 47  in (1.2  m) deep, drive

the rod into the ground to bedrock level and

bury any remainder horizontally at least 2 ft

(600  mm) below ground level. If the bedrock is

less than 47 in (1.2 m) deep, bury the rod

horizontally at least 2 ft (600 mm) below

ground level (ref. article 10-702, 3d of the

Canadian Electricity Code C22.10-99).

The rod must be connected to the wire de-

scribed above. It is recommended to let the rod

going out of the ground to connect it. The wire

length must not exceed 50  ft (15 m).

10

 f

(

)

3 m

2 ft
(

)

600 mm

Burying 
the rod

Bedrock

<

4

7

 i

n

 (

1

.2

 m)

EARTH

GND

3-meter

metal rod

10 ft 
(

)

3 m

2 ft
(

)

600 mm

10 ft (

)

3 m

<4

7

 i

n

 (

1

.2

 m

)

SIREN

+

ALARM  SYSTEM

It is extremely important that the

earth ground terminal be con-

nected to a proper ground to pro-

tect the electronic components

from damage due to lightning

surges and electrostatic dis-

charges. Do not use the electrical

ground for this purpose.

If outdoor connections are used,

mount the enclosure as close as

possible to the entry point of the

outdoor wiring.

An improper earth ground connec-

tion immediately voids the system

warranty without further notice.

1.4.4 Siren Output

The terminals marked SIREN are for the siren.

The voltage supplied is 12  VDC with a maxi-

mum current of 1.5 A. Note that the battery

must be hooked up if a siren is used. The F5

fuse (2A slow blow) is connected to this

output. Make sure the positive wire is con-

nected to the positive terminal of the siren.

Содержание Agri Alert 400

Страница 1: ...Alarm System User s Manual ...

Страница 2: ... by the manufacturer Every effort has been made to ensure that this manual is complete accurate and up to date The information contained in it is however subject to change without notice due to further developments Manufacturer Viatron Electronics 5200 Armand Frappier St Hubert Quebec Canada J3Z 1G5 ...

Страница 3: ...4 Siren Output 7 2 USER INTERFACE 8 2 1 Faceplate 8 2 2 Internal Switches 9 3 CONFIGURING THE ZONES 10 3 1 Enabling Disabling the Zones 10 3 2 Setting Zone Contacts 10 3 3 Setting the Recognition Time 10 3 4 Setting the Alarm Output Status 10 4 CONTROLLER S OPERATION 11 4 1 Cancelling Acknowledging an Alarm 11 4 2 Activate Bypass a Zone 11 5 APPENDIX 12 Appendix A Fuse Types 12 Appendix B Maximum ...

Страница 4: ...ber AA 400 Serialnumber Dateinstalled 1 2 Installation Procedure What you need AA 400 system including an independentbatteryenclosure 12VDC 7 5AHsealedleadacid battery 16 5VAC 40VAtransformer To avoid electrical shocks and equipment damage turn off the breaker on which is connected the unit before configuring the main board or making connections to the terminals Step 1 Determine where you want to ...

Страница 5: ... the sides Make sure they are not obstructed Battery Box 6 150 mm plastic tubing cable holder cable holder Alarm System 6 3 8 162 mm 149 mm 5 7 8 4 1 2 115 mm 6 3 8 162 mm 5 7 8 149 mm Mountthebatteryenclosure41 2 115 mm from the AA 400 enclosure Use the plastic tubing provided to run the wires from the battery to the alarm system These wires are providedwiththesystem Thebareendhooks up to the AA ...

Страница 6: ...ground False alarms can result if the ground wires are not properly connected Z1 Z2 Z3 Z4 COM COM Zone 1 sensor Zone 2 sensor Zone 3 sensor Zone 4 sensor 1 4 2 Supply Inputs 1 4 2 1 AC Power Connection The terminals marked 16 VAC on the main boardareusedforconnectingthetransformer Thetransformerprovidedwiththesystemisa 16 5 VAC 40 VA transformer It must be pluggedintoa120 VAC 60 Hzoutlet TheF2 fus...

Страница 7: ...connectit Thewire length must not exceed 50 ft 15 m 10 ft 3 m 2 ft 600 mm Burying the rod Bedrock 47 in 1 2 m EARTH GND 3 meter metal rod 10 ft 3 m 2 ft 600 mm 10 ft 3 m 47 in 1 2 m SIREN ALARM SYSTEM It is extremely important that the earth ground terminal be con nected to a proper ground to pro tect the electronic components from damage due to lightning surges and electrostatic dis charges Do no...

Страница 8: ... button until the LED turns red solid or flashing Blank spaces Write down the description of each zone in the spaces provided Blank spaces Cancel button Zone status LEDs Bypass activate buttons System status LEDs ZoneStatusLEDs SystemStatusLights Status LED Meaning Alarm This LED is lit when an alarm condition is detected AC Power This LED is lit when the device is powered properly Low Battery Thi...

Страница 9: ... switch ALWAYS turn off power to the AA 400 before opening the enclo sure When the alarm system is shipped all internal switches are set to OFF ON OFF 1 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 ON OFF 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 8 9 16 OFF ON 1 ZONE 1 2 ZONE 2 3 ZONE 3 4 ZONE 4 5 ZONE 1 6 ZONE 2 7 ZONE 3 8 ZONE 4 9 ZONE 1 10 ZONE 2 11 ZONE 3 12 ZONE 4 13 SIREN ALWAYS ON INTERMITTENT ON 10 SEC OF...

Страница 10: ...the AA 400 must use the same type of contact as for the wireless module ON OFF 8 7 6 5 OFF ON 5 ZONE 1 6 ZONE 2 7 ZONE 3 8 ZONE 4 NO NC 3 3 Setting the Recognition Time Therecognitiontimeisthetimeanalarminput must be active before it constitutes a valid alarm condition It can be set to 0 or to 30 seconds Set internal switches 9 12 properly to assign the desired recognition time to each zone refer ...

Страница 11: ...ed Blinking red LED Zone enabled Status alarm active Solid red LED Zone enabled Status no alarm 4 2 Activate Bypass a Zone TheAA 400canactivateorbypassindividual zones Whenazoneisbypassed thepilotlight associated with it turns yellow and no alarm detectionisperformedonthezoneinput when azoneisactive thepilotlightturnsredandthe AA 400 monitors the zone input Only the zones that are enabled with int...

Страница 12: ...ft 500 m N A FUSE NUMBER FUSE TYPE FONCTION F2 5A fast blow 5 x 20 mm AC Power Connection F4 1A fast blow 5 x 20 mm 12 VDC Output F5 2A slow blow 5 x 20 mm Siren Output 0 C 32 F 20 C 68 F 350mA minimum charge Siren and 12VCD output not used 17 hours 20 hours 3500mA maximum charge Siren 1500mA 12VCD 750mA 1 2 hour 1 hour Temperature Current mA 5 APPENDIX Appendix A Fuse Types Appendix B Maximum wir...

Страница 13: ...ry Rechargeable sealed lead acid 12V 7 5 AH Outputs Siren 12VDC 1 5A max Fuse F5 2A slow blow 12VDC 750mA DC max Fuse F4 1A fast blow Operating temperature 32 to 104 F 0 to 40 C Indoor use only Pollutiondegree 2 Installationcategory 2 Altitude 7900 ft max 2000 meters max Humidity 95 max Cleaning Gentle soap and water ...

Страница 14: ...GND Zone 1 sensor 16Vac 40VA Transformer ON OFF 1 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 ON OFF 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 8 9 16 Battery Box 12VDC Optional Wireless Alarm Receiver WM3000 Rx max 750mA Alarm Supply max 1 5 A Zone 2 sensor Zone 3 sensor Zone 4 sensor 10 ft metal rod 3 m 7 5 AH ...

Страница 15: ...15 AA 400 rev 02 ...

Страница 16: ...M 890 00458 rev 02 REV 02 ...

Отзывы: