background image

3

 

98MANAL574   Rev. F 

 

INSTALLATION REQUIREMENTS AND CAUTIONS

 

1.  All electrical and pressure connections should be compatible with the above specifications.  
2.  The Model 574 is susceptible to sensor damage by being dropped, struck, or installed in a high vibration 

environment.  

3.  Installation should occur only after electrical (input power) and line pressure is verified as being off and at zero.  
4.  The product’s internal electrical circuitry is isolated from case ground.  It is not recommended that the case or 

ground of the unit be connected to the input or output of the product or wiring system.  Ground loops and line 
noise will affect the product’s performance and may cause internal electrical failure.  

5.  Due to the effects of gravity on oil fill of the sensor, it is recommended that the product be mounted as shown 

above.  If the product is mounted on its side (pressure port facing up) the effect of gravity will show as drift or 
product instability  

6.  Small amounts of vacuum will not damage the product.  If a high vacuum is desired, both pressure ports must be 

equally drawn down at the same time.  

7.  The pressure flanges are removable to facilitate cleaning of the pressure cavities.  Care should be taken not to 

damage diaphragms when flanges are removed.  When reassembled, the bolts should be torqued in a criss-
cross pattern; for process flanges with 7/16 x 20 nuts & bolts to 22.0 ft. lbs. or for standard flanges with 5/16 x 24 
nuts & bolts to 11.5 ft. lbs.  

8.  Process media and cleaning solution should be compatible with 316 SS, Viton O-Ring.  
9.  All products should be protected from direct or continued exposure to fluids at the electrical connection.  The 

electrical connections on the Model 574 have been designed to be terminated in a junction box or encased in 
conduit. In applications where moisture or fluid contamination is possible, the use of a NEMA rated connection 
box is recommended for connection termination.  

10.  At no time should an object be inserted into the pressure port or pressed against the sensing area to deflect the 

sensor (to test or simulate pressure) as permanent fill loss and/or damage to the sensing diaphragm may occur.  

11.  During installation it is recommended that the unit be mounted to allow fluids or contamination to flow away from 

the module screw area, so as not to collect on the screw heads or sockets.  (Do not mount the unit facing up.)  

12.  When shipped in quantities, units should be packaged individually to eliminate possible damage.  
13.  To preserve the integrity of the hermetic design, the units have no field replaceable or repairable parts.  
 

BASIC OPERATION & INTERNAL CALIBRATION CIRCUIT 

(See Maintenance and Repair for calibration frequency recommendations.)  

Note: 

The casting of the module has raised numbers at the adjustment screw positions.  Those numbers reflect 

 

the following function of the assigned screw. 

 

Screw 1: Top Left, Coarse Zero Pot (CCW - Lower, CW - Raise) 

 

Screw 2: Top Right, Fine Zero Pot (CCW - Lower, CW - Raise) 

 

Screw 3: Lower Left, Internal Cal. Activation Pot (12 or 6 o’clock position – Disengage; 3 o’clock position - Engage) 

 

Screw 4: Lower Right, Span Adjustment Pot (CCW - Lower, CW - Raise)  

1.  Outside of using the calibration circuit or the availability of a metrology lab for obtaining a pressure (Full Scale) 

reading, no object should be used to physically move the sensor.  

2.  Once proper connections and power are applied, the unit should begin to function.  
3.  Check the zero output (4.00 mA) with the performance certificate to verify readings. If it is out of specification 

from the performance certificate, use the coarse and fine zero adjustment screws to obtain the proper reading.  

4.  With no pressure applied, engage the calibration circuit by slowly rotating the calibration screw until the current 

output rises to about 8.80 mA’s (standard calibrated range). Check the reading with the performance certificate. 
If the reading is off, adjust the span screw to raise or lower the reading – return the calibration circuit to the 
original position.  

5.  When making zero and/or span adjustments, there may be some interaction between the zero and span 

readings - repeat adjustments if needed.  

6.  Always return the calibration screw to off or full CCW position before installing the transmitter into the application. 

Note: This is a common reason for incorrect readings at start-up. The calibration circuit must be deactivated in 
order for the product to perform properly.  

7.  Once the product has been tested and functionality verified, the power and meter connections may be removed 

and the product reconnected to the instrumentation loop.  

NON-STANDARD RANGE (NSR) CALIBRATION 

 

Definition 

 

NSR: A non-standard range is a alternate scaled reading requested by the customer.  Through the use of a single 
transmitter, numerous pressure ranges can be set-up.  The Model 574 can be scaled down to any pressure range to 
five times the original range.  Only NSR requests for ranges less than the sensor rated range are recommended and 
in most cases possible.  The NSR is possible due to the ability of the adjustment screws to alter where the zero and 
span will fall. Refer to the below example for field NSR calibration.  

 
 
 

Содержание 574

Страница 1: ...L574 Rev F INSTALLATION DATA MANUAL MODEL 574 PRESSURE TRANSMITTER 199 Fire Tower Drive Tonawanda NY 14150 Int l 1 716 629 3800 Toll Free 1 800 688 0030 Fax 1 716 693 9162 www viatran com solutions viatran com ...

Страница 2: ...ct our Application Engineers for assistance Remove and retain all instruction manuals and performance certificates that are shipped with the product These documents provide important information on the product s calibration operation safety precautions recommended maintenance re calibration requirements repair service instructions and warranty information These documents are updated from time to t...

Страница 3: ...ble damage 13 To preserve the integrity of the hermetic design the units have no field replaceable or repairable parts BASIC OPERATION INTERNAL CALIBRATION CIRCUIT See Maintenance and Repair for calibration frequency recommendations Note The casting of the module has raised numbers at the adjustment screw positions Those numbers reflect the following function of the assigned screw Screw 1 Top Left...

Страница 4: ... mists dusts or contaminants could cause them to become frozen in place causing the module to become locked and non usable This would render external adjustment difficult at best Replacement magnets are available if this problem occurs Hence a visual inspection of the calibration pots should take place on a 2 to 4 week schedule or when extreme environmental conditions require it 4 NEVER Strike a p...

Страница 5: ...lve 12 months from the date of shipment provided that Viatran s obligation hereunder shall be limited to correcting any defective workmanship and or replacing any defective material f o b factory No allowance will be made for any expense incurred for correcting any defective workmanship and or material without written consent by Viatran This warranty is in lieu of all other warranties expressed or...

Отзывы: