4
2.
Boiler usage and advantages
Cast-iron sectional gas boiler VIADRUS G 90 is equipped with law-emission atmospheric burner and is
intended for burning pf low-pressure natural gas. The boiler is made in B
11BS
design it means it is equipped
with combustion gases reflux fuse.
It is suitable first of all for heating the middle–sized and bigger premises.
The use of gas valves with an automatic control and watch of the gas cap tightness at the burner makes it
possible to install the boilers in the boiler rooms of categories I and II. The boiler is only made as the hot-
water boiler with a forced circulation and work overpressure up to 400 kPa (4 bar). Before the dispatch the
boiler is tested for tightness by 800 kPa (8 bar) testing overpressure.
Boiler advantages:
1. High service life of the cast-iron boiler drum.
2. Simple operation and maintenance.
3. Reliable security and control elements
4. Gas combustion efficiency 92 %.
5. As a standard equipped with combustion gases reflux fuse.
6. Silent running and law electricity consumption.
7. Gas connected either from the left-hand side or from the right-hand side.
8. Connection of the output and return water either from the left-hand side or from the right-hand side (it
doesn’t apply to the 8-sectional version).
9. Possibility to connect the boiler in an cascade.
10. Possibility to equip with an equitherm regulation.
11. Two-stage burner (nominal/ reduced output).
12. Possible delivery in a decomposed state.
The content of harmful substances in the combustion gases is significantly lower than the values prescribed
by the guideline MŽP 05 – 98 „Environmentally friendly product “ and meets the requirements of the most
strict European standards.
3.
Boiler technical data
Tab. no. 1 Dimensions, service temperatures and electric parameters of the boiler
Number of sections
pc
8
10
12
15
Appliance category
I
2H
Weight
kg
242
339
399
489
Water space volume
l
27,7
34,3
40,9
50,8
Diameter of smoke socket
mm
200
200
225
250
Boiler overall dimensions - depth
mm
995
1155
1315
1555
- width x height
mm
878,5 x
1160
941x1160
Max. water operating overpressure
kPa (bar)
400 (4)
Min. water operating overpressure
kPa (bar)
30 (0,3)
Testing water overpressure
kPa (bar)
800 (8)
Max. heating water operating temperature
°C
85
Min. return water temperature
°C
50
Input gas overpressure
mbar
18
Noise level
dB
Does not exceed the 55 dB (A) level
Chimney draught
mbar
Minimum 0,025
Boiler connections - heating water
Js
6/4"
- return water
Js
6/4"
- gas
Js
1/2"
1“
Connecting voltage
1/N/PE 230 V AC 50 Hz TN-S
Electric input
W
50
Electric protection
IP 40
Содержание G 90 Series