Installation & Operation Manual
TABLE - 4B
Typical water heating installations
General plumbing rules:
1. Check all local codes.
2. For serviceability of water heater, always install unions.
3. Always pipe pressure relief valve to an open drain.
4. Locate system air vents at highest point of system.
5. Expansion tank must be installed near the water heater and
on the suction side of the system pump.
6. Support all water piping.
4
Water connections
0
5
10
15
20
50
60
70
80
90
100
Press Drop i
n
Feet H
ead
Flow in Gallons Per Minute
Pressure Drop Chart
Models 500-1000
TABLE - 4C
0
5
10
15
20
25
70
80
90
100
110
120
Pr
ess Dr
op
in
Feet Head
Flow in Gallons Per Minute
Pressure Drop Chart
Models 1500-2000
Water heater requirements
The installer must ensure that the water heater is supplied
with adequate flow without excessive temperature rise. Flow
rates exceeding the maximum recommended flow will result in
erosion of the water heater tubes.
TABLE - 4D
ACCEPTABLE TEMPERATURE RISE
Model
Min
∆
°
F
Max
∆
°
F
500
11
18
750
17
25
1000
23
30
1500
28
35
2000
38
41