Overview 2
VES, LLC
eView Installation Manual VF3510-00, Revision E01.06
8 of 16
Lower-Control-Pad
The figure below illustrates the eView lower-control-pad:
Figure 2-3
Lower-Control-Pad
Key
Name
Description
1
Re-Sound Alarm
Re-sounds the alarm in Access Level 2 when sounders are muted with the
Alarm Silence button.
2
Alarm Silence
Silences NACs connected to the eView after receiving authorization
through Access Level 2.
3
Panel Sounder
Silence
Mutes the internal buzzer of the eView. No other sounder outputs are
affected by this operation.
4
Lamp Test
Tests front-panel indicators and the internal buzzer by illuminating all LEDs
while darkening the front-panel display and sounding the buzzer.
5
Reset
Resets latching inputs such as fire and pre-alarm events after receiving
authorization through Access Level 2. Fault events are non-latching inputs
and cannot be cleared by the Reset button. Non-latching inputs are cleared
when faults are cleared.
6
Fire Drill
Provides a fire drill for the eView after receiving authorization through
Access Level 2. During the drill:
•
The “On Test” LED illuminates continuously
•
The “Fire” LEDs blink
•
The internal buzzer sounds intermittently
•
The display provides the message,
“FIRE DRILL:FIRE DRILL ZONE 00*
To stop the fire drill:
1 Press 4 to display the “SET ACCESS LEVEL 2 MENU”.
2 Provide Access Level 2 authorization.
3 Press Reset or Fire Drill on the lower-control-pad.
7
Programmable
Function
Activates inputs, outputs or actions defined in the configuration when in
Access Level 2.