AIRBEAM Wall Extract Units
Installation, Operation and Maintenance Manual
ORIGINAL INSTRUCTIONS
!
Contents
Page
1
Introduction
1
2
Receipt of Goods
1
3
Installation
1
4
Wiring
2
5
Maintenance
3
1
Introduction
The AIRBEAM series is a range of extract wall units, with a
duty range of between 0.11 and 1.2m³/s. The range offers an
unobtrusive design, with a number of outlet/housing options.
Standard operating temperature of the unit is -20 to +50°C
and the fans are rated at IP54.
For further technical details regarding dimensions and
weights contact VES on
08702 404340
, quoting the sales
order (SO) number and the unit type as found on the unit
nameplate or visit
www.ves.co.uk
.
2
Receipt of Goods
Immediately upon receipt of goods check for possible
damage in transit paying particular attention to fan impeller.
Prior to installation please check to ensure smooth rotation
of the impeller after transit. Also check to ensure that any
ancillary items are included. These will normally be
supplied fitted or in the case of small items taped to the
unit.
In the event of any damage having occurred or if any item is
found missing, it is essential to inform VES Andover Ltd.
within
3 working days
of delivery quoting sales order (SO)
number and the unit type as found on the unit nameplate.
After this period we will be unable to accept any claim for
damaged or missing goods.
Fig. 1
Unit arrangement
Top: Louvre unit
Bottom: Cowl unit
3
Installation
The entire system must be considered for safety purposes
and it is the responsibility of the installer to ensure that all of
the equipment is installed in compliance with the
manufacturer’s recommendations, with due regard to the
current HEALTH AND SAFTEY AT WORK ACT and conforms
to all relevant statutory regulations. Where a unit is installed
so that a failure of components could result in injury to
personnel, precautions should be taken to prevent such an
injury.
IMPORTANT
Only experienced fitters should undertake this work. Take
necessary safety precautions when working in elevated positions
The AIRBEAM unit is specifically designed for wall mounting,
in the vertical plane only. A hole must be cut in the wall to
the following dimensions prior to installation; note the
difference in opening size between louvre and cowl housings
see
fig 2
. Trim the wall opening as required to make good.
1
VES Ref: ID660
Issue C
May 2015
Louvre unit
Remove the front louvre from the wall sleeve. To ease
installation, the fan should also be removed by removing the
fan fixing bolts, ensuring after installation the fan plate is
reattached in the correct position. Insert the unit in the
opening from the outside of the ventilated area, taking care
to avoid damaging the external finish (reducing the unit’s
resistance to corrosion).
External
Louvre
Axial fan,plate and
guard assembly
External
Cowl
Case, backdraught
flaps & fan plate
assembly
Backdraught
flap/plate
!
IMPORTANT
It is the responsibilty of the installer to ensure that the unit is
installed in a manner which will not result in injury or damage
to either the unit or property.
When selecting the location for your Airbeam, it is critical to
ensure there are no immediate obstructions to the airflow as
this will cause a loss of performance.
These products contain rotating parts and electrical
connections which can be a danger and could cause injury,
although unlikely as all fans are fitted with motor side guards.
The axial fans utilised in the Airbeam range also generate
noise; it is advised that if activities have to be conducted in
close proximity to the working units the noise level should be
taken into account.
Taking the previously mentioned points into consideration, it
is advised that this unit should installed out of normal reach
of personnel.
Fig. 2
Approximate unit weights & opening dims
Lined hole
size (mm)
Weight (kg)
Lined hole
size (mm)
Weight (kg)
315
505 x 505
21
340 x 340
12
355
505 x 505
25
395 x 395
15
400
595 x 595
23
450 x 450
12
450
595 x 595
28
495 x 495
16
500
675 x 675
33
575 x 575
19
560
745 x 745
39
635 x 635
25
630
835 x 835
42
710 x 710
25
Unit
Louvre
Cowl