VES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF

Tel: 08702 404340  Fax: 08702 404550  E-mail: [email protected] Web: www.ves.co.uk

AIRBEAM Wall Extract Units

Installation, Operation and Maintenance Manual

ORIGINAL INSTRUCTIONS

 

!

Contents

Page

1

Introduction

1

2

Receipt of Goods

1

3

Installation

1

4

Wiring

2

5

Maintenance

3

1

Introduction

The AIRBEAM series is a range of extract wall units, with a
duty range of between 0.11 and 1.2m³/s. The range offers an
unobtrusive design, with a number of outlet/housing options.
Standard operating temperature of the unit is -20 to +50°C
and the fans are rated at IP54.

For further technical details regarding dimensions and
weights contact VES on 

08702 404340

, quoting the sales

order (SO) number and the unit type as found on the unit
nameplate or visit 

www.ves.co.uk

.

2

Receipt of Goods

Immediately upon receipt of goods check for possible
damage in transit paying particular attention to fan impeller.
Prior to installation please check to ensure smooth rotation
of the impeller after transit. Also check to ensure that any
ancillary items are included. These will normally be
supplied fitted or in the case of small items taped to the
unit.

In the event of any damage having occurred or if any item is
found missing, it is essential to inform VES Andover Ltd.
within 

3 working days 

of delivery quoting sales order (SO)

number and the unit type as found on the unit nameplate.
After this period we will be unable to accept any claim for
damaged or missing goods.

Fig. 1

Unit arrangement
Top: Louvre unit
Bottom: Cowl unit

3

Installation

The entire system must be considered for safety purposes
and it is the responsibility of the installer to ensure that all of
the equipment is installed in compliance with the
manufacturer’s recommendations, with due regard to the
current HEALTH AND SAFTEY AT WORK ACT and conforms
to all relevant statutory regulations. Where a unit is installed
so that a failure of components could result in injury to
personnel, precautions should be taken to prevent such an
 injury.

IMPORTANT

Only experienced fitters should undertake this work. Take
necessary safety precautions when working in elevated positions

The AIRBEAM unit is specifically designed for wall mounting,
in the vertical plane only. A hole must be cut in the wall to
the following dimensions prior to installation; note the
difference in opening size between louvre and cowl housings
see 

fig 2

. Trim the wall opening as required to make good.

1

VES Ref: ID660

Issue  C

May 2015

Louvre unit

Remove the front louvre from the wall sleeve. To ease
installation, the fan should also be removed by removing the
fan fixing bolts, ensuring after installation the fan plate is
reattached in the correct position. Insert the unit in the
opening from the outside of the ventilated area, taking care
to avoid damaging the external finish (reducing the unit’s
resistance to corrosion).

External
Louvre

Axial fan,plate and
guard assembly

External
Cowl

Case, backdraught
flaps & fan plate
assembly

Backdraught
flap/plate

 

!

IMPORTANT

It is the responsibilty of the installer to ensure that the unit is
installed in a manner which will not result in injury or damage
to either the unit or property.

When selecting the location for your Airbeam, it is critical to
ensure there are no immediate obstructions to the airflow as
this will cause a loss of performance.

These products contain rotating parts and electrical
connections which can be a danger and could cause injury,
although unlikely as all fans are fitted with motor side guards.
The axial fans utilised in the Airbeam range also generate
noise; it is advised that if activities have to be conducted in
close proximity to the working units the noise level should be
taken into account.

Taking the previously mentioned points into consideration, it
is advised that this unit should installed out of normal reach
of personnel.

Fig. 2 

Approximate unit weights & opening dims

Lined hole  

size (mm)

Weight (kg)

Lined hole  

size (mm)

Weight (kg)

315

505 x 505 

21

340 x 340

12

355

505 x 505 

25

395 x 395

15

400

595 x 595

23

450 x 450

12

450

595 x 595

28

495 x 495

16

500

675 x 675

33

575 x 575

19

560

745 x 745

39

635 x 635

25

630

835 x 835

42

710 x 710

25

Unit

Louvre

Cowl