Shutdown Delay (Sdd):

Selects the amount of time delay between remote shutdown signal
and the thermostat going into shutdown mode.

0 seconds Default, immediate

 

Programmable Range:  0 seconds to 200 minutes

Setback Override (Sbo):

Selects the amount of time the remote setback or shutdown can be
overridden by the occupant pressing the up, down or fan buttons.

0 minutes Default, no override

 

Programmable Range:  0 minutes to 8 hours,

 

in 15 minute increments

If Remote Pipe Sensor (rS3) is set to EA the following
parameters are available:

Heating Activation Temperature (HAt):

Selects the pipe temperature that activates heating and fans.

85.0°F (29.5°C) Default

 

Programmable Range:  75.0°F to 99.0°F (24.0°C to 37.0°C)

Cooling Activation Temperature (CAt):

Selects the pipe temperature that activates cooling and fans.

65.0°F (18.5°C) Default

 

Programmable Range:  40.0°F to 70.0°F (4.5°C to 21.0°C)

Fan Coil Functions (CFg):

Selects the desired 2-pipe fan coil system.

2Ps - Default, 2-pipe single valve fan coil

 

2PE - 2-pipe with electric heat

 

2Pn - 2-pipe valveless

NOTE:  Refer to Installation Instructions for further explanations

Valve Purge Frequency (Pgf):

Selects the length of time between valve purges.

60 minutes Default

 

Programmable Range:  30 minutes to 120 minutes (2 hours),

 

in 10 minute increments

Valve Purge Duration (Pgd):

Selects the length of time that the valve is in purge mode.

180 seconds (3 minutes) Default

Programmable Range:  30 seconds to 300 seconds (5 minutes),

 

in 10 second increments

To restore factory presets:

Press

 and hold the fan and down arrow buttons while sliding the 

°F/°C switch to the opposite side. 
00 will appear on the display.

Press

 either the up or down arrow button to locate the erase

mode 

Access code 92.

Press

 the fan button upon reaching the code.

All and erase

 will appear on the display.

To restore 

ALL

 factory presets, simply press the fan button when

ALL appears on the display.  The program will exit also.

To restore individual parameters, press either the up or down
arrow button until the parameter is reached.  Press the fan button
and the factory preset is restored.  
To exit, press the up or down arrow buttons until End and ERASE 
appear on the display.
Press the fan button to exit.

5

9510-1237  Rev -
9-22-14