Shutdown Delay (Sdd):
Selects the amount of time delay between remote shutdown signal
and the thermostat going into shutdown mode.
0 seconds Default, immediate
Programmable Range: 0 seconds to 200 minutes
Setback Override (Sbo):
Selects the amount of time the remote setback or shutdown can be
overridden by the occupant pressing the up, down or fan buttons.
0 minutes Default, no override
Programmable Range: 0 minutes to 8 hours,
in 15 minute increments
If Remote Pipe Sensor (rS3) is set to EA the following
parameters are available:
Heating Activation Temperature (HAt):
Selects the pipe temperature that activates heating and fans.
85.0°F (29.5°C) Default
Programmable Range: 75.0°F to 99.0°F (24.0°C to 37.0°C)
Cooling Activation Temperature (CAt):
Selects the pipe temperature that activates cooling and fans.
65.0°F (18.5°C) Default
Programmable Range: 40.0°F to 70.0°F (4.5°C to 21.0°C)
Fan Coil Functions (CFg):
Selects the desired 2-pipe fan coil system.
2Ps - Default, 2-pipe single valve fan coil
2PE - 2-pipe with electric heat
2Pn - 2-pipe valveless
NOTE: Refer to Installation Instructions for further explanations
Valve Purge Frequency (Pgf):
Selects the length of time between valve purges.
60 minutes Default
Programmable Range: 30 minutes to 120 minutes (2 hours),
in 10 minute increments
Valve Purge Duration (Pgd):
Selects the length of time that the valve is in purge mode.
180 seconds (3 minutes) Default
Programmable Range: 30 seconds to 300 seconds (5 minutes),
in 10 second increments
To restore factory presets:
Press
and hold the fan and down arrow buttons while sliding the
°F/°C switch to the opposite side.
00 will appear on the display.
Press
either the up or down arrow button to locate the erase
mode
Access code 92.
Press
the fan button upon reaching the code.
All and erase
will appear on the display.
To restore
ALL
factory presets, simply press the fan button when
ALL appears on the display. The program will exit also.
To restore individual parameters, press either the up or down
arrow button until the parameter is reached. Press the fan button
and the factory preset is restored.
To exit, press the up or down arrow buttons until End and ERASE
appear on the display.
Press the fan button to exit.