Field Programming Parameters:  Access Code 79

Explanation of Codes:

Temperature Scale (Unt):  

Selects scale parameter that will be shown

F - Default,°F

 

C - °C

On Power Interrupt (OPi):

Selects whether the thermostat will go into economy mode or
occupied mode after a power interrupt

EC – Default, thermostat will go into economy mode after

 

a power interrupt

 

OC – thermostat will go into occupied mode after a power

 

interrupt

Display Temperature (dSp):  

Selects which temperature is shown on display

SP - Default, display will show setpoint only

 

rt - display will show room temperature unless either up or 

 

down arrow button is pressed.  Then the display will show

 

setpoint.

 

Srt - display will toggle between room temperature and

 

setpoint.  Display will revert to setpoint when either the up or

 

down arrow button is pressed.

Temperature Control Mode (HAc):

USr - Default, switch selectable, heat only, auto changeover

 

or cool only

 

Aut - auto mode only

 

CL - cool mode only

 

Ht - heat mode only

Stop Function Enabled (Stp):

  

Selects whether or not thermostat can be turned off by pressing
the fan button

Ena – Default, enabled, press fan button until Stp appears

 

on display

 

dis – disabled

Economy Function Enabled (ECo):

Selects whether or not thermostat can be manually placed in
economy mode by pressing the fan button

Ena – Default, enabled, press fan button until Eco and

 

ECON appears on display

 

dis – disabled

Comfort Setpoint (CS):  

Selects setpoint default temperature when thermostat powers up
or returns to comfort mode from economy mode

72.0°F (22.0°C) Default

Programmable Range:  60.0°F to 85.0°F (15.5°C to 29.5°C)

Cooling Limit (LC):

Selects minimum room temperature in cooling

65.0°F (18.5°C) Default

Programmable Range:  60.0°F to 85.0°F (15.5°C to 29.5°C)

Heating Limit (LH):

Selects maximum room temperature in heating

85.0°F (29.5°C) Default

Programmable Range:  60.0°F to 85.0°F (15.5°C to 29.5°C)

Freeze Protection (FP):

Selects freeze protection enabled or disabled

Ena – Default, enabled at 40°F

 

dis – disabled

Fan Purge Timer (FPt):

Selects the amount of time the fan will continue to run after a 
heating or cooling call.

30 seconds Default

Programmable Range:  0 (Off) to 180 seconds (3 minutes),

 

in 10 second increment

Clear Logged Data (CLr):

Selects whether or not the logged run time data will be reset to 0’s

NO – default, no reset

 

yEs – reset

Energy Savings Preset (ESp):

Presets the stepped back functions according to the required energy
savings level.  One of three presets can be chosen or skip this
parameter and go directly to the Sbr parameter to begin choosing
other non-preset settings.
 

L1 – (least energy savings)

Setback Ramping (Sbr):  enabled
First Setback Timer (FSt):  480 minutes (8 hours)
Second Setback Timer (SSt):  60 minutes
Degrees Per Setback (dPs):  1.0°

This means that after 8 hours of no motion sensed the thermostat
will begin to step back at a rate of 1.0° every 60 minutes until either
the unoccupied cooling limit (UCL) or the unoccupied heating limit
(UHL) is reached.
 

L2 – (moderate energy savings)

Setback Ramping (Sbr):  enabled
First Setback Timer (FSt):  240 minutes (4 hours)
Second Setback Timer (SSt):  60 minutes
Degrees Per Setback (dPs):  1.0°

This means that after 4 hours of no motion sensed the thermostat
will begin to step back at a rate of 1.0° every 60 minutes until either
the unoccupied cooling limit (UCL) or the unoccupied heating limit
(UHL) is reached.

L3 – Default (most energy savings)

Setback Ramping (Sbr):  disabled
First Setback Timer (FSt):  60 minutes

This means that after 1 hour of no motion sensed the thermostat
will go directly to either the unoccupied cooling limit (UCL) or the
unoccupied heating limit (UHL)

Setback Ramping (Sbr):

Selects setback function to step back to unoccupied setpoints or to
go directly to unoccupied setpoints.

dis - Default, disabled, directly to unoccupied setpoints

Ena – enabled, steps back to unoccupied setpoints

First Setback Timer (FSt):

When in occupied mode, selects the amount of time when no motion
is detected before the setpoint begins to be stepped back by the
degrees per setback

60 minutes Default

 

Programmable Range:  1 minute to 720 minutes (12 hours),

in 15 minute increments

3