Verve Living Systems is a registered brand of
ZENO Controls, LLC
p4
(877) 874-8774
To Link or Unlink a Sensor
When a Door/Window Sensor is linked, the position of the
magnet indicates to the transceiver which type of sensor profile
is being used.
1. Set the desired transceiver to Accept a Link.
2.
Do one of the following according to the desired profile:
A. Entry door for occupancy detection, place the magnet
beside the sensor (closed position).
B. Window or patio door for HVAC control, move the mag-
net way from the sensor (open position).
C. Closet door for single load control, move the magnet
away from the sensor (open position).
3. Press the Link button on the sensor once.
The Set button on the transceiver
will be solid green for 3 seconds.
The device is now linked.
Installing Supplemental Battery (optional)
If the sensor is installed where the light levels are consistently
too low or there are days of darkness, battery power can be
used to supplement the solar energy harvester. Only use a
CR1216 battery.
1. Press the tab lock to release the
sensor from the mounting bracket.
2. Slide the sensor about ½” (1 cm)
and remove it from the mounting
plate.
3. Insert the battery with the positive
pole (+) up and slide it between
the two contact terminals with
your finger.
WARNING: Ensure the battery is properly oriented. Improper
handling of lithium batteries may result in heat generation,
explosion, or fire.
4. Replace the sensor on the mount-
ing plate and slide it until it snaps
into place.
5. Open and close the contact to test
for power.
6. There should be a faintly audible
click and a fast LED blink.
Tab lock
Notch
Tab lock
Notch
Contact Terminals
Contact Terminals
Troubleshooting
Problem
Solution Checklist
The sensor does not
generate a wireless
message
▪
Verify there is a faintly audible click when the
contact is closed and opened
▪
Verify the LED blinks once when the contact is
closed and opened
▪
Verify the solar cell is charged properly
▪
Check that the magnet is oriented to the sen-
sor properly
▪
Check that the alignment arrows are not
spaced more than .25 inch (6.4 mm)
The linked device
does not respond
to wireless mes-
sages
▪
Check for environment or range issues. Tip:
Reorienting the sensor may overcome adverse
RF conditions
▪
Verify the device is linked
▪
Check the transceiver connection and the wir-
ing for errors
▪
Check if appropriate devices are linked accord-
ing to good system planning
902 MHz:
Contains:
315 MHz:
Contains:
FCC: SZV-STM311U
FCC: SZV-STM311C
IC: 5713A-STM311U
IC: 5713A-STM311C
This device complies with part 15 of the FCC rules and Industry Canada ICES-003. Operation is subject
to the following two conditions: (1) This device may not cause harmful interference, and (2) this device
must accept any interference received, including interference that may cause undesired operation.
IMPORTANT! Any changes or modifications not expressly approved by the party responsible for
compliance could void the user’s authority to operate this equipment.
Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio exempts
de licence. L’exploitation est autorisée aux deux conditions suivantes: (1) l’appareil ne doit pas produire
de brouillage, et (2) l’utilisateur de l’appareil doit accepter tout brouillage radioélectrique subi, meme