Verve EDWS Скачать руководство пользователя страница 4

Verve Living Systems is a registered brand of 

ZENO Controls, LLC

p4

[email protected] 

(877) 874-8774

To Link or Unlink a Sensor

When a Door/Window Sensor is linked, the position of the 

magnet indicates to the transceiver which type of sensor profile 

is being used.
1.  Set the desired transceiver to Accept a Link.
2. 

Do one of the following according to the desired profile:

A.  Entry door for occupancy detection, place the magnet 

beside the sensor (closed position). 

B.  Window or patio door for HVAC control, move the mag-

net way from the sensor (open position). 

C.  Closet door for single load control, move the magnet 

away from the sensor (open position).

3.  Press the Link button on the sensor once.  

 

The Set button on the transceiver 

will be solid green for 3 seconds. 

The device is now linked.

 

Installing Supplemental Battery (optional)

If the sensor is installed where the light levels are consistently 

too low or there are days of darkness, battery power can be 

used to supplement the solar energy harvester. Only use a 

CR1216 battery. 
1.  Press the tab lock to release the 

sensor from the mounting bracket.

2.  Slide the sensor about ½” (1 cm) 

and remove it from the mounting 

plate.

3.  Insert the battery with the positive 

pole (+) up and slide it between 

the two contact terminals with 

your finger.

 

 

WARNING: Ensure the battery is properly oriented. Improper 

handling of lithium batteries may result in heat generation, 

explosion, or fire.

4.  Replace the sensor on the mount-

ing plate and slide it until it snaps 

into place. 

5.  Open and close the contact to test 

for power.

6.  There should be a faintly audible 

click and a fast LED blink.

Tab lock

Notch

Tab lock

Notch

Contact Terminals

Contact Terminals

Troubleshooting

Problem

Solution Checklist

The sensor does not 

generate a wireless 

message

 

Verify there is a faintly audible click when the 

contact is closed and opened

 

Verify the LED blinks once when the contact is 

closed and opened

 

Verify the solar cell is charged properly

 

Check that the magnet is oriented to the sen-

sor properly

 

Check that the alignment arrows are not 

spaced more than .25 inch (6.4 mm)

The linked device 

does not respond 

to wireless mes-

sages 

 

Check for environment or range issues. Tip: 

Reorienting the sensor may overcome adverse 

RF conditions

 

Verify the device is linked 

 

Check the transceiver connection and the wir-

ing for errors

 

Check if appropriate devices are linked accord-

ing to good system planning

 

902 MHz: 

Contains: 

 

315 MHz: 

Contains: 

 

 

FCC:  SZV-STM311U 

 

FCC: SZV-STM311C 

  

 

IC:  5713A-STM311U  

 

IC: 5713A-STM311C

This device complies with part 15 of the FCC rules and Industry Canada ICES-003. Operation is subject 

to the following two conditions: (1) This device may not cause harmful interference, and (2) this device 

must accept any interference received, including interference that may cause undesired operation. 

IMPORTANT! Any changes or modifications not expressly approved by the party responsible for 

compliance could void the user’s authority to operate this equipment. 
Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio exempts 

de licence. L’exploitation est autorisée aux deux conditions suivantes: (1) l’appareil ne doit pas produire 

de brouillage, et (2) l’utilisateur de l’appareil doit accepter tout brouillage radioélectrique subi, meme 

si le brouillage est susceptible d’en compromettre le fonctionnement. 

IMPORTANT! Tous les changements ou modifications pas expressément approuvés par la partie 

responsable de la conformité ont pu vider l’autorité de l’utilisateur pour actioner cet équipment.

Door/Window Sensor • Installation Guide

Содержание EDWS

Страница 1: ...ur 100 lux for 60 actuations hour Charge Time for Full Charge 21 hours 200 lux after startup 42 hours 200 lux cold start Operating Life in Dark ness after full charge 174 hours heartbeat only 67 hours 10 actuations hour 10 hours 100 actuations hour EEP EnOcean Equipment Profile D5 00 01 Maximum Sensor Gap 0 25 inch 6 4 mm Dimensions Sensor 3 15 L x 0 83 W x 0 59 D 80 mm x 21 mm x 15 mm Dimensions ...

Страница 2: ...cribed in the Planning section NOTE For easy access and handling it is recommends that the sensor be linked to a transceiver before installing it see the Linking section 3 Install the sensor on the interior side of the fixed frame A Remove the mounting bracket from the sensor estimated time 20 minutes Tab lock Notch Tab lock Notch B Position the mounting bracket and mark the two mount ing screw dr...

Страница 3: ... link message The awaiting transceiver receives and stores the link permanently so the devices can interact to provide a variety of intelligent control options Sensor Profiles The sensor profile determines how the sensor is used within the system whether it is for occupancy detection HVAC control or single load control How the sensor interacts with other devices depends on where it is installed an...

Страница 4: ...hooting Problem Solution Checklist The sensor does not generate a wireless message Verify there is a faintly audible click when the contact is closed and opened Verify the LED blinks once when the contact is closed and opened Verify the solar cell is charged properly Check that the magnet is oriented to the sen sor properly Check that the alignment arrows are not spaced more than 25 inch 6 4 mm Th...