All Generators up to 30 KW On the Ground (Gravity) Foundation Kit Installation (P/N D1001-0020-0062)
This 4’ x 9’ platform is designed for all ATT approved generators up to the Generac 30 KW Diesel. The
generator should be installed in the center of the platform and in any orientation that will fit. Grounding
locations are on all four sides to support any site layout. Platform includes a rodent guard for all generators that
need it. Feet are adjustable and can be buried. See
Grade Considerations
1.
Ground/gravel should be normally dry and have good drainage.
2.
Ground/gravel should be level or very close.
All Generators Up To 30KW On The Ground (Gravity) Foundation Kit Installation Procedure
1.
The Generator On The Ground (Gravity) Foundation Kit ships assembled so lift and set it on grade in
desired location. If using a forklift make sure the forks are longer than four feet to get under the entire
frame. The weight of the frame is 611 lbs.
2.
Level the frame by adjusting the leveling hardware between the frame and the eight footers. Start by
leveling the four corners first then adjust the remaining footers. Once leveling is achieved, secure the
hardware.
3.
Cut and layout rodent guard on the platform to fit generator foot print.
4.
Lift and set the generator, up to 30 KW, onto the platform and rodent guard then anchor in place.
5.
Connect all conduits and cabling to generator.
6.
Connect a ground cable from the generator platform to the WIC ground bar.
Figure 27:
Generators On the Ground (Gravity) Foundation Kit