Version Nr. 1-1 - 23.08.2017

Doc. Nr. 994020009

4 / 14

4. Technical information

The cooling unit is intended to be used as a complementary accessory to larger industrial
equipment. The unit is used where heat needs to be dissipated from electrical control cabinets or
similar enclosures in order to protect heat sensitive components. It is not intended for household use.
The unit has two completely separate air circuits which ensure that the clean cabinet air does not
come into contact with the ambient air which may well be dirty or polluted. Control cabinet cooling
units can dissipate large quantities of heat from sealed enclosures such as electrical enclosures into
the ambient air and at the same time reduce the cabinet internal temperature to below that of the
ambient air.
The unit can function without problems in extreme ambient conditions (e.g. dusty and oily air) with
a standard operating temperature ranging between -20°C and +55°C. Units can be ordered with an
additional electrical cabinet heater. For the cooling capacities and evironmental ratings please refer to
the type plate data.

5. Technical data

Customer order number

1.920.906.0

Order Number

4020009

Cooling capacity L35L35

1,8 kW

Compressor

Rotary piston compressor

Refrigerant / GWP

R134a / 1430

Refrigerant charge

650 g / 23 oz

High / low pressure

45 / 44 bar
440 / 140 psig

Temperature range

+20°C - +55°C

Mounting

External

Housing Material

Aluminum

Dimension HxWxD

1,066 x 486 x 157 (173) mm

Weight

36 kg

Voltage / Frequency

230 V ~ 50/60 Hz

Rated current

5.6 A

Current L35L35

5.6 A

Starting current

22 A

Nominal power L35L35

1,22 kW

Max. power

1,25 kW

Fuse

2 x 16 A (T)

Connection

Cable

IP class EN 60529

External circuit: IP 44
Internal circuit: IP 55

Approvals

CE, cURus, SA32278

Содержание OC 4020009

Страница 1: ...regulations 2 3 Safety instructions 3 4 Technical information 4 5 Technical data 4 7 Mounting 5 8 Electrical connection 6 9 Controller Layout Description 8 10 Wiring diagram 9 11 Taking into operatio...

Страница 2: ...instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a specific pictogram such as one of the following High electric voltage Indicates...

Страница 3: ...ds to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid safety regulati...

Страница 4: ...e ambient air The unit can function without problems in extreme ambient conditions e g dusty and oily air with a standard operating temperature ranging between 20 C and 55 C Units can be ordered with...

Страница 5: ...ooling unit enclosure air suction hole must be installed in the highest possible point When installing the unit on a door ensure it can take the weight Before drilling the enclosure ensure the fixing...

Страница 6: ...equire an external power source if wired to operate external components indicator lamps switches The load on these contacts is not to exceed 30V DC 4 A or 120 250V AC 4 A If wired to external componen...

Страница 7: ...on or off via a door contact switch terminal 3 4 When delivered the door contact terminals are bridged To connect the door contact switch Remove the bridge from terminals 3 4 Connect the door contact...

Страница 8: ...tional HC Heater control AC Alarm control TC Temperature control OS Optional Sensor DC Door contact AO Alarm output PI Power in CO Compressor out CC Capacitor compressor AFO Umgebungsl fter aus CAF Ko...

Страница 9: ...tral line fuse FL Live line fuse Temp Control temperature adjustment potentiometer Alarm Alarm temperature adjustment potentiometer Heater Heater temperature adjustment potentiometer 1 2 Alarm contact...

Страница 10: ...Version Nr 1 1 23 08 2017 Doc Nr 994020009 10 14...

Страница 11: ...erefore be allowed to stand for at least 30 min before being connected to the mains and taken into operation Upon connection the internal fan will start working If the temperature inside the enclosure...

Страница 12: ...protector triggered Verify if ambient temperature is too high clean condenser Refrigerant leakage Contact dealer service center Excessive condensate Enclosure door open Ambient air gets into the encl...

Страница 13: ...ould be returned in the original packing or in a packing case and must be strapped to a pallet If the unit cannot be returned in the original packing please ensure that A space of at least 30 mm must...

Страница 14: ...94020009 14 14 15 Parts supplied 1 x Outdoor cabinet air conditioner 1 x Instruction manual 1 x CE Conformity declaration 1 x Connector with bridged door contacts 1 x Lid deflector with fasteners 1m P...