3
•
Filtering:
a)
Peak-peak voltage is ≤ 250mV at 1-100MHz and normal output voltage.
b)
Psophemetic noise voltage is ≤ 2mV between 5-100% of the maximum load (output voltage > 56 VDC).
c)
Wideband noise is < 20mV rms between 25HZ-20kHz (test according to ETS300132).
d)
Output noise according to Telcordia GR-947-CORE: < 38 dBrnC (between 5-100% of the maximum load, output voltage >
56 VDC).
•
Ripple Attenuation: Ripple attenuation is better than +24dB, input to output and f < 360Hz.
1.2.2
DC Input Ratings
•
Voltage: Nominal -48 volts DC.
•
Nameplate Rating: -41 to -58.5 VDC, 53A max.
•
Inrush Current: The peak value of the inrush current does not exceed 2 times the maximum steady-state peak value.
•
Input Regulation: ≤ ±0.2% when the load is 100% at -42 to -58.5 VDC input and temperature is +25°C.
•
Temperature Coefficient: ≤ ±0.02%/°C over the specified operating temperature range.