Vertiv™ NetSure™ DC/DC Converter Module User Manual 

 

11 

Table 3.1:  Converter Module Troubleshooting 

Symptom 

Possible Cause(s) 

Suggested Action(s) 

 

Power Indicator 

(Green) Off 

No input voltage. 

Make sure there is input voltage. 

Internal input fuse open. 

Replace the converter. 

 

Protection Indicator 

(Yellow) On 

DC input under/over voltage. 

Correct the DC input voltage to within the acceptable range. 

Moderate load sharing imbalance.  Check if the converter is properly seated in the shelf.  If this does not 

correct the fault, replace the converter. 

Converter not inserted into the 

slot completely. 

Remove and properly insert the converter. 

Converter over-temperature 

protection. 

Fan rotor blocked:  remove any object that may be blocking the fan. 
Ventilation blocked (inlet or outlet):  remove any object that may be 

blocking the inlet or outlet. 
Ambient temperature too high or rectifier inlet too close to a heat 

source:  lower the ambient temperature or relocate the heat source. 

Converter in ECO Standby Mode 

when ECO Mode is active in 

controller. 

-- 

Protection Indicator 

(Yellow) 

Flashing 

Loss of communication with 

controller (the converter can 

provide power). 

Check the communication cables. 
Remove and properly insert the converter. 

 

Alarm 

Indicator 

(Red) On 

Severe load sharing imbalance. 
Converter output disabled for any 

reason, including overvoltage 

shutdown. 

Remove the converter, wait 30 seconds or more (until the LEDs on 

the converter extinguish), then re-insert the converter.  If converter 

fails to start, shuts down again, or load sharing imbalance persists; 

replace the converter. 

Converter addresses 

contradictory. 

Replace the converter. 

Alarm Indicator 

(Red) Flashing 

Fan not operating (converter 

shuts down). 

Replace the converter. 

 

3.2

 

Replacement Procedures 

3.2.1

 

Converter Module Replacement 

Converters can be inserted or removed with power applied (hot swappable). 

 

NOTE!

  

Each converter locks into a module mounting shelf by means of a latch located on the bottom of the module.  The 

latch and converter handle are interactive.  Pushing the handle up into the module’s front panel causes the latch to extend to 
the locking position; pulling the handle down out from the module’s front panel causes the latch to retract.  See Figure 2.3. 

 

DANGER!  

Take care when removing a converter that was in operation, as converter surfaces could be very hot. 

 

WARNING!  

To prevent damage to the latching mechanism, ensure the handle is in the open position when installing or 

removing a converter.  NEVER hold the handle in the closed position when installing a converter into a shelf. 

Procedure 

 

NOTE!

  

Refer to Figure 2.3 as this procedure is performed. 

 

1.

 

Performing this procedure may activate external alarms. Do one of the following. If possible, disable these alarms.  If these 
alarms cannot be easily disabled, notify the appropriate personnel to disregard any alarms associated with this system while 
this procedure is performed. 

Содержание Netsure

Страница 1: ...NetSure DC DC Converter Module User Manual Specification Number 1C48582000P3 Model Number C48 58 2000P3...

Страница 2: ...specifically described in this document The products covered by this instruction manual are manufactured and or sold by Vertiv This document is the property of Vertiv and contains confidential and pro...

Страница 3: ...s 5 1 2 4 Compliance Information 5 1 2 5 Standard Features 6 1 2 6 Mechanical Specifications 7 2 Operation 7 2 1 Local Indicators 7 2 2 Converter High Voltage Shutdown and Lockout Restart 8 2 3 Conver...

Страница 4: ...SI OSHA This admonition is not used for situations that pose a risk only to equipment data or service even if such use appears to be permitted in some of the applicable standards OSHA ALERT Alerts the...

Страница 5: ...rdously high the input power can deliver large amounts of current DC Output and Battery Voltages DANGER This system produces DC power and may have a battery source connected to it Although the DC volt...

Страница 6: ...static sensitive components discharge all static electricity from yourself by wearing a wrist strap grounded through a one megohm resistor Some wrist straps have a built in one megohm resistor no exte...

Страница 7: ...verage 2000W peak The C48 58 2000P3 can provide 2000 watts peak and 1600 watts average This is based on a cyclic load profile of 2000 watts for 7msec and 600 watts for 3msec Output Characteristics Ref...

Страница 8: ...48 VDC and temperature range is from 10 C to 55 C c Dynamic Response The dynamic response time at rated input and output voltage is 200us and overshot 5 for load changes at 50 25 50 and 50 75 50 d Th...

Страница 9: ...GR 947 CORE 38 dBrnC between 5 100 of the maximum load output voltage 56 VDC Ripple Attenuation Ripple attenuation is better than 24dB input to output and f 360Hz 1 2 2 DC Input Ratings Voltage Nomina...

Страница 10: ...4 91 166 75 70 28 90 94 49 210 29 80 33 19 94 02 260 81 90 37 55 93 48 319 92 100 41 90 94 96 280 34 53 5 VDC 10 3 30 90 79 50 36 20 6 35 94 38 61 48 30 9 43 95 31 76 89 40 12 57 95 32 102 32 50 15 73...

Страница 11: ...as the office environment 1 2 4 Compliance Information Safety Compliance This unit meets the requirements of UL 62368 1 Standard for Information Technology Equipment and is UL Recognized as a power s...

Страница 12: ...y The converter can be inserted or removed from a live DC power system with no damage When the converter is plugged into the system the sub system output voltage will not be affected Cooling Each conv...

Страница 13: ...put Voltage Protection High Temperature Protection Thermal Derating Address Code Date Software Version Hardware Version Imbalance Output Current 1 2 6 Mechanical Specifications Weight 1 13kg 2 49 lbs...

Страница 14: ...onverter The converter may also be restarted from the controller Refer to the controller s documentation 2 3 Converter Current Limit When setting total converter current limit the set point to each co...

Страница 15: ...energized might represent a hazard during servicing after operation of the fuse WARNING To prevent damage to the latching mechanism ensure the handle is in the open position when installing or removin...

Страница 16: ...r is properly seated in the shelf If the current sharing imbalance still persists following the verification suggested above replace the converter exhibiting the current imbalance 3 1 2 Converter Modu...

Страница 17: ...ve the converter wait 30 seconds or more until the LEDs on the converter extinguish then re insert the converter If converter fails to start shuts down again or load sharing imbalance persists replace...

Страница 18: ...odule completely into the shelf 7 Push the handle up into the module s front panel This will lock the module securely to the shelf Tighten the captive screw on the handle 8 Certain functions i e conve...

Страница 19: ...NetSure DC DC Converter Module User Manual Connect with Vertiv on Social Media https www facebook com vertivI https www instagram com vertiv https www linkedin com company vertiv https www twitter com...

Страница 20: ...e trade names trademarks or registered trademarks of their respective owners While every precaution has been taken to ensure accuracy and completeness here Vertiv Group Corp assumes no responsibility...

Отзывы: