background image

 
 

 

Vertiv

 

|

 

NetSure™ SCC Controller User Manual (UM1M520HNA)

 

|

 

Rev. H 

22 

IP Address:  

 

                                    

Subnet Mask:   

                                    

Default Gateway:                                      
Example: 

IP Address:  

 

192.168.1.2 

Subnet Mask:   

255.255.255.0 

Default Gateway:  192.168.1.1 

4.

 

If DHCP is enabled in the controller,

 select the "Obtain an IP address automatically" in your local 

computer’s network settings. 

If DHCP is disabled in the controller,

 select the "Use the following IP address" button in your local 

computer’s network settings.  Then change your local computer’s network settings using the information 
you acquired in Step 3, except that the last part of the IP address needs to be replaced with any 
different number. 

IP Address:  

 

                                    

Subnet Mask:   

                                    

Default Gateway:                                      
Example: 
IP Address:  

 

192.168.1.3 

Subnet Mask:   

255.255.255.0 

Default Gateway:  192.168.1.1 

5.

 

Select 

OK

.  Note that you may have to reboot your local computer for the settings to take effect.  Follow 

any instruction you see on the screen. 

Disabling Proxy Server Settings to Enable a Connection to the Controller over an Intranet Network (if 

required) 

 

NOTE!  

This procedure needs to be performed only when the controller is connected to an Intranet and 

the User’s computer is set to access the Intranet through a proxy server.  Note that if the controller is 
connected to the Internet and the User’s computer is connected to an Intranet, the User may not be able 
to disable the proxy server and access the controller. 

If the controller’s Ethernet Port is connected to your company’s Intranet Network and your computer is also 
connected to the Intranet Network but requires access via a proxy server, you must disable the proxy server 
settings to access the controller.  Follow the procedure below to disable the proxy server settings. 

Procedure 

1.

 

Launch “Internet Explorer”. 

2.

 

Select 

Internet Options

 from the 

Tools

 menu.  The “Internet Options” window opens.  In the “Internet 

Options” window, select the 

Connections

 Tab. 

Содержание NetSure SCC

Страница 1: ...NetSure SCC Controller User Manual UM1M520HNA Revision H Specification Number 1M520HNA Model Number M520H...

Страница 2: ...ethods tools and materials to be used in performing procedures not specifically described in this document This document may contain confidential and or proprietary information of Vertiv Group Corp an...

Страница 3: ...ode 10 Rectifier and BBU Module Data Monitoring 10 Alarm Detection and Reporting 10 Alarm Logs 10 Specifications 11 Operation 12 SNMP Access 12 SCC Controller Interaction with the RMS 12 Local Indicat...

Страница 4: ...Vertiv NetSure SCC Controller User Manual UM1M520HNA Rev H 4 Replacement Procedures 32 SCC Controller Replacement 32 Troubleshooting 34...

Страница 5: ...d ANSI OSHA This admonition is not used for situations that pose a risk only to equipment data or service even if such use appears to be permitted in some of the applicable standards OSHA ALERT Alerts...

Страница 6: ...ngs and other metal objects c Prior to contacting any uninsulated surface or termination use a voltmeter to verify that no voltage or the expected voltage is present Check for voltage with both AC and...

Страница 7: ...is necessary Read and follow wrist strap manufacturer s instructions outlining use of a specific wrist strap 3 Do not touch traces or components on equipment containing static sensitive components Han...

Страница 8: ...Vertiv NetSure SCC Controller User Manual UM1M520HNA Rev H 8 This page is intentionally blank...

Страница 9: ...the SCC Controller Imminent Power Failure Notification The imminent power fail signal triggers 1 ms before the DC bus collapses It triggers when the combination of rectifiers and batteries on the bus...

Страница 10: ...irements are cycled through the group of rectifiers controlled by this feature to provide uniform operating times for each rectifier Rectifier and BBU Module Data Monitoring The SCC Controller monitor...

Страница 11: ...185 F Humidity Capable of operating in an ambient relative humidity range of 5 to 95 non condensing Altitude The SCC Controller is capable of operating in an altitude range of 200 feet to 10 000 feet...

Страница 12: ...ing an SNMP interface NOTE The rectifier and BBU modules will continue to operate if the SCC Controller fails The rectifier and BBU modules will work if the system is powered up without an SCC Control...

Страница 13: ...System DC Output Voltage mV average of non zero values reported by all rectifier and BBU units Get System DC Output Current A average of non zero values reported by all rectifier and BBU units Get DC...

Страница 14: ...te Get Set configSystemTimeEx syntax DateAndTime Get Set configTrapTimeFormat Advanced Data SCC Controller to from the RMS Table 6 Detailed Rectifier Data for Each Rectifier Get Set Field Get Set Rect...

Страница 15: ...Get Running Time hours Get Fan Status ok failed Get Rated Battery Output Power 90 Seconds W Get Product Model Number Get Serial Number Get Remaining Available Capacity Get Estimate Time to Fully Char...

Страница 16: ...date time field One set uses a human readable date time format as a text string the second set uses the DateAndTime format Table 8 Alarms Traps AC Mains Failure AC Mains Failure Ended Rectifier Failu...

Страница 17: ...of expected BBUs when the configuration complete flag is set Battery Failure Ended Sent when the failure condition clears EPO Signal Received Sent when the EPO signal is received See EPO Emergency Pow...

Страница 18: ...r the rectifier battery with the alarm if applicable Table 11 Historical Alarms Description Index The alarm index number StartTime The date time that the alarm triggered as a string StartTimeEx The da...

Страница 19: ...Local Indicators Locations Table 12 SCC Controller Local Indicators Indicator Normal State Fault State Fault Cause Status Green On Off No input voltage to the SCC Controller Internal hardware problem...

Страница 20: ...ation It can also set batteryLearningModeStart N to 0 to command the BBU to skip this learning mode request If the BBU starts calibration the SCC will send an SNMP trap to indicate that the BBU is not...

Страница 21: ...e Controller Directly to your Computer An Ethernet port is provided in the system This port supports Dynamic Host Configuration Protocol DHCP function Connect your computer to the Ethernet port after...

Страница 22: ...ettings to take effect Follow any instruction you see on the screen Disabling Proxy Server Settings to Enable a Connection to the Controller over an Intranet Network if required NOTE This procedure ne...

Страница 23: ...cedure Internet Explorer version 5 5 or newer is required It is best to view the WEB Interface at 1280 x 1024 resolution In newer versions of Internet Explorer you may need to turn Compatibility View...

Страница 24: ...ress ENTER to reopen the login window NOTE User names and passwords are case sensitive By default the User Name and Password combination is admin and 654321 respectively 2 After entering a valid User...

Страница 25: ...label The date code must be 17 10 or later for BBUs that have compatible firmware The date code must be 15 09 or later for BBUs that can have their firmware upgraded 2 Place BBU modules in a 12 V mod...

Страница 26: ...Vertiv NetSure SCC Controller User Manual UM1M520HNA Rev H 26 Figure 2 BBU Date Code Label Date Code Label Sample Serial Number with Date Code 15 Represents the Year 07 Represents the Month...

Страница 27: ...e 3 Web Interface Homepage Setting Static IP SNMP Community Strings and DHCP Communications Parameters From the Homepage you can set Static IP SNMP Community Strings and DHCP communications parameters...

Страница 28: ...e file into the controller Press the Back to the Homepage button Downloading Firmware into the SCC Controller Press the GO TO FIRMWARE DOWNLOAD MODE button Select OK The following window opens Figure...

Страница 29: ...e Alarms Log Webpage From the Homepage you can access the Active Alarms page The Active Alarms page lists any active alarm recorded by the SCC Controller The Active Alarms page refreshes approximately...

Страница 30: ...roller User Manual UM1M520HNA Rev H 30 Alarm History Log Webpage From the Homepage you can access the Alarm History page Alarm events are recorded on the Alarm History page The alarm history log can a...

Страница 31: ...ng slot without sliding it in completely 3 Loosen the captive fastener on the SCC Controller s latch mechanism Pull the latch mechanism to pivot it out of the SCC Controller s front panel this also re...

Страница 32: ...to the Configuration Label on the side of the replacement SCC Controller for the Configuration Part Number 2 Performing this procedure may activate alarms Notify the appropriate personnel to disregard...

Страница 33: ...Vertiv NetSure SCC Controller User Manual UM1M520HNA Rev H 33 12 Notify appropriate personnel that this procedure is finished and to act upon any future alarms associated with this system...

Страница 34: ...n Power is on and SCC is running No action required Status Indicator Green Off No input voltage Make sure there is input voltage Internal hardware problem Replace the SCC Controller Warning Indicator...

Страница 35: ...Vertiv NetSure SCC Controller User Manual UM1M520HNA Rev H 35 This page is intentionally blank...

Страница 36: ...Vertiv com Vertiv Headquarters 1050 Dearborn Drive Columbus OH 43085 USA UM1M520HNA RH 10 19...

Отзывы: