Installing Rectifiers
The rectifier is hot swappable. It can be installed with the system operating.
CAUTION!
This rectifier module contains Double pole fusing; parts of the equipment that remain
energized might represent a hazard during servicing after operation of the fuse. If the rectifiers are
connected to a 3-phase system, the neutral line should also have a fuse.
WARNING!
To prevent damage to the latching mechanism, ensure the handle is in the open position
when installing or removing a module. NEVER hold the handle in the closed position when installing a
module into a shelf.
Procedure
NOTE!
as this procedure is performed.
1.
Place the rectifier into an unoccupied mounting slot without sliding it in completely.
2.
Click the rectifier handle in order to pop it forward out of the rectifier's front panel (this will also retract
the latch mechanism located on the underside of the rectifier). Refer to
illustration.
3.
Push the rectifier completely into the shelf.
4.
Push the handle into the front panel of the rectifier. This locks the rectifier securely to the shelf.
5.
Repeat the above steps for each rectifier being installed in the system.
6.
After the rectifiers are physically installed in the mounting shelf(s), they are ready for operation
immediately after power is supplied to them.
7.
Certain functions (i.e. rectifier current limit, rectifier addressing) may require adjustment when adding or
replacing a rectifier Module. Refer to the Power System documentation for instructions.
Figure 16:
Installing a Rectifier