Typical Input Data (1R483500e): 60 Hz input.
a)
System output is initially adjusted to 54.48 VDC as measured at the system sense points at 50 % of
full load and nominal input. “Percent of Full Load” refers to percent of 60 amperes.
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
Efficiency
%
Heat
Dissipation
BTU/Hr
208
0
0.42
87
11
0.125
--
34.5
25
4.20
872
853
0.977
95.28
132.7
50
8.20
1700
1690
0.994
96.00
221.2
75
12.34
2553
2546
0.997
95.48
378.6
100
16.66
3441
3435
0.998
94.31
651.1
110
18.32
3781
3775
0.998
93.68
800.1
120
18.36
3790
3782
0.998
93.29
854.6
240
0
0.49
118
11
0.920
--
34.2
25
3.66
877
850
0.969
95.59
123.2
50
7.11
1704
1684
0.988
96.34
201.0
75
10.65
2547
2535
0.995
95.86
343.9
100
14.34
3423
3414
0.997
94.90
576.4
110
15.75
3758
3748
0.997
94.36
703.8
120
15.79
3768
3757
0.997
93.91
765.4
277
0
0.54
149.6
8.6
0.572
--
29.35
25
3.09
856.4
840.6
0.982
96.29
212.11
50
6.1
1691.8
1675
0.990
96.29
212.11
75
9.15
2535.6
2524.8
0.996
95.77
364.85
100
12.26
3394.5
3388.8
0.998
94.94
584.78
110
13.58
3753.8
3748
0.988
94.51
702.18
120
13.58
3753.9
3748.9
0.994
94.52
700.84
b)
Maximum Input Current: at 100% of full load with output adjusted to 58 VDC as measured at the
shelf output terminals.
Nominal Input
Voltage
Input
Voltage
Input Current
(Amperes)
208/240/277
176
21.60