NetSure Rectifier Module User Manual (UM1R482000e / 11BU1360YY)

 

|

 

Rev. J 

22 

 

Cooling:  Each rectifier contains a fan for front-to-back force air-cooling. 

a)

 

Fan Fault Protection:  The rectifier shuts down and its alarm indicator (red) flashes if the fan fails.  
Fan failure is detected and reported to controller.  The fans are field replaceable. 

b)

 

Fan Control:  When the input voltage is within a normal range, the built-in processor adjusts the fan’s 
speed according to the rectifier ambient and internal temperature.  This feature can be disabled 
allowing the fan to run at full speed regardless of temperature. 

 

Paralleling:  This rectifier may be connected in parallel with any rectifier of the same polarity and 
adjusted to the same output voltage. 

 

Communication Failure:  The rectifier’s protection indicator (yellow) will flash should it experience a 
communication failure.  The failure information will be reported to the controller and the controller will 
process the failure accordingly.  During a communication failure, in order to protect the battery, the 
rectifier output voltage will automatically be adjusted as follows. 

-

 

The rectifier default factory output voltage is 53.5V. 

-

 

Once power is applied to the rectifier and the rectifier is recognized by the controller, the output 
voltage is updated to the setting programmed into the controller. 

-

 

If communications with an SCU+ controller is lost, rectifier output voltage goes to a default value 
programmed into the controller (this is a separate programmable parameter from the output voltage 
setting). 

-

 

If communications with an ACU+ or NCU controller is lost, rectifier output voltage goes to the last 
communicated float output voltage setting in the controller (the last communicated float output 
voltage setting is stored in the rectifier). 

-

 

The rectifier will revert to normal operation once normal communication to the controller is restored. 

 

Rectifier Output Current Imbalance: 

a)

 

When the average current of all rectifiers is greater than 20% of full rated current, and the difference 
between local rectifier current and average current is greater than 16% of full rated current, the 
yellow protection indicator will illuminate. 

b)

 

When the average current of all rectifiers is greater than 10% of full rated current, and local rectifier 
current is less than 1.5% of full rated current, then the red fault indicator will illuminate. 

 

Monitoring Function:  The rectifier has a built-in advanced DSP that monitors and controls the operation 
of the rectifier.  The DSP also communicates with the controller in real time through the CAN bus.  

Table 

13

 lists the different commands and information exchanged between the rectifier and the controller. 

Содержание NetSure R48-2000

Страница 1: ...NetSure Rectifier Module User Manual UM1R482000e 11BU1360YY Revision J Specification Number 1R482000 1R482000e 1R482000H Model Number R48 2000 R48 2000e R48 2000H...

Страница 2: ...nd materials to be used in performing procedures not specifically described in this document This document may contain confidential and or proprietary information of Vertiv Group Corporation and its r...

Страница 3: ...Overview 7 Specifications 7 DC Output Ratings 7 AC Input Ratings 11 Environmental Ratings 19 Compliance Information 20 Standard Features 20 Mechanical Specifications 23 Operation 24 AC Input Protectio...

Страница 4: ...avoided ANSI OSHA This admonition is not used for situations that pose a risk only to equipment data or service even if such use appears to be permitted in some of the applicable standards OSHA ALERT...

Страница 5: ...pable of producing fatal electrical shock DC Output and Battery Voltages DANGER This system produces DC power and may have a battery source connected to it Although the DC voltage is not hazardously h...

Страница 6: ...ary Read and follow wrist strap manufacturer s instructions outlining use of a specific wrist strap 3 Do not touch traces or components on equipment containing static sensitive components Handle equip...

Страница 7: ...Mode unless load increases to the point where the product of load current and output voltage is approximately 2000W Constant Power Mode As load increases above approximately 2000W non adjustable outpu...

Страница 8: ...varies with changes in input voltage and output voltage It uses an advanced power limitation method The lower input threshold is 85 VAC The rectifier can provide its maximum rated power 2000W as long...

Страница 9: ...00 and R48 2000H or 55 C 131 F R48 2000e the rectifier will not shut down Rather the rectifier limits its maximum output power to maintain the temperature of the power conversion circuit within design...

Страница 10: ...2000 and R48 2000H or 55 C 131 F R48 2000e and 80 C 176 F will result in output power decrease Operation above 80 C 176 F is considered abnormal and should be used on a temporary1 basis only 1 Tempora...

Страница 11: ...ut and 20 to 70 of rated load 3 R48 2000 1R482000 and R48 2000H 1R482000H Psophometric noise is 1 mV at 5 to 100 of rated load 4 R48 2000e 1R482000e Psophometric noise is 2 mV typical at 20 to 70 of r...

Страница 12: ...5 1980 5 99 80 94 90 344 98 110 10 32 2149 8 2139 5 99 52 94 58 395 71 120 10 36 2151 8 2147 5 99 80 94 22 423 81 240 0 0 38 106 6 32 5 30 50 110 89 25 2 13 509 3 494 5 97 10 95 37 78 10 50 4 15 996...

Страница 13: ...5 99 85 94 21 424 15 240 0 0 33 74 3 26 0 35 00 88 72 25 2 11 505 1 494 5 97 90 95 42 77 24 50 4 13 991 9 982 0 99 00 96 21 126 91 75 6 15 1474 3 1467 5 99 54 95 97 201 88 100 8 24 1975 3 1970 0 99 73...

Страница 14: ...0 99 94 89 93 766 53 240 0 0 33 77 8 27 7 35 60 94 52 25 2 23 534 1 525 0 98 30 89 70 184 52 50 4 29 1028 8 1026 0 99 73 91 90 283 66 75 6 38 1529 5 1529 0 99 97 91 90 422 83 100 8 58 2055 2 2055 0 99...

Страница 15: ...2 99 96 89 75 780 85 240 0 0 29 65 9 27 41 00 92 13 25 2 22 531 1 525 98 86 89 86 181 62 50 4 29 1028 7 1027 99 83 91 88 284 42 75 6 37 1531 3 1531 99 98 91 85 425 70 100 8 57 2057 2 2057 99 99 91 20...

Страница 16: ...99 96 91 42 645 48 240 0 0 362 86 5 36 5 42 20 124 54 25 2 20 526 5 516 0 98 00 91 47 150 24 50 4 26 1018 4 1015 0 99 67 93 11 238 56 75 6 31 1513 6 1513 0 99 96 93 09 356 94 100 8 46 2029 2 2029 0 9...

Страница 17: ...0 99 97 91 45 642 57 240 0 0 32 75 0 36 0 48 00 122 84 25 2 18 523 3 516 5 98 70 91 36 152 32 50 4 23 1016 2 1014 0 99 78 93 16 236 62 75 6 30 1513 3 1513 0 99 98 93 03 359 86 100 8 46 2026 2 2026 0 9...

Страница 18: ...Vertiv NetSure Rectifier Module User Manual UM1R482000e 11BU1360YY Rev J 18 Figure 7 Efficiency Curve R48 2000e 1R482000e Figure 8 Efficiency Curve R48 2000 1R482000...

Страница 19: ...arth Capable of withstanding surges per ANSI IEEE C 62 41 1980 Category B3 across the input terminals NOTE This level of protection is a widely used standard for telecommunications power equipment As...

Страница 20: ...ltage Mode unless load increases to the point where the product of load current and output voltage is approximately 2000W Constant Power Mode As load increases above approximately 2000W non adjustable...

Страница 21: ...value before the HVSD restart timer expires the rectifier shuts down and locks out Manual restart is then required by turning power to the rectifier off or by removing the rectifier waiting until the...

Страница 22: ...ized by the controller the output voltage is updated to the setting programmed into the controller If communications with an SCU controller is lost rectifier output voltage goes to a default value pro...

Страница 23: ...n Fail Protection Alarms such as Input Voltage Protection Inner DC Bus Voltage Protection High Temperature Protection Thermal Derating AC Derating AC Fail Imbalance Output Current Address Code Date So...

Страница 24: ...iption There are three 3 indicators located on the rectifier s front panel The functions of these indicators are as shown in Table 14 NOTE DC voltage must be present at the rectifier output terminals...

Страница 25: ...internal output fuse open Rectifier addresses contradictory Flashing Fan not operating rectifier module shuts down Installing Rectifiers The rectifier is hot swappable It can be installed with the sy...

Страница 26: ...tation for instructions Figure 11 Installing a Rectifier TROUBLESHOOTING AND REPAIR Troubleshooting Rectifier Current Sharing Imbalance When multiple rectifiers are operating in parallel and the curre...

Страница 27: ...y object that may be blocking the inlet or outlet Ambient temperature too high or rectifier inlet too close to a heat source lower the ambient temperature or relocate the heat source Rectifier in ECO...

Страница 28: ...n the underside of the rectifier This unlocks the rectifier from the shelf Refer to Figure 11 for latch mechanism illustration 3 Slide the rectifier out by pulling forwards 4 Place the replacement rec...

Страница 29: ...the remainder of this procedure 4 On this rectifier remove the front panel by removing the screws securing the front panel to the chassis and by unplugging the fan from the printed circuit card 5 For...

Страница 30: ...Vertiv NetSure Rectifier Module User Manual UM1R482000e 11BU1360YY Rev J 30 Figure 12 Rectifier Fan Replacement...

Страница 31: ...Vertiv NetSure Rectifier Module User Manual UM1R482000e 11BU1360YY Rev J 31 This page is intentionally blank...

Страница 32: ...VertivCo com Vertiv Headquarters 1050 Dearborn Drive Columbus OH 43085 USA UM1R482000e 11BU1360YY RJ 08 17...

Отзывы: