Vertiv NetSure R48-2000 Скачать руководство пользователя страница 21

 
 

Vertiv

 

|

 

NetSure Rectifier Module User Manual (UM1R482000e / 11BU1360YY)

 

|

 

Rev. J 

21 

 

Output Protection: 

a)

 

Overload / Reverse Current:  The rectifier has a 63A fuse in the negative output DC bus.  This fuse is 
not customer replaceable.  The rectifier can be plugged into or pulled out of a shelf while operating, 
without damage or opening the fuse. 

b)

 

Current Limiting:  The rectifier has a current limit function.  The current limit point can be set 
between the range of 0 to 41.7 A, adjustable via the controller.  The current limit accuracy is ±1.5A 
for R48-2000e and ±1.0A for R48-2000 and R48-2000H when the output voltage ranges from 42 to 
58 V. 

c)

 

Advanced Current Limit Function:  The rectifier has an advanced Current Limit Function.  When a 
short circuit occurs at the rectifier output terminals, the rectifier will keep its output current at a 
constant value (value that is configurable via the controller).  This function effectively protects the 
rectifier and the equipment connected to the rectifier.  When the short circuit fault is cleared, the 
rectifier will automatically restore back to normal operation. 

d)

 

High Voltage Shutdown: 

1.

 

Adjustable Control:  If rectifier output voltage exceeds an adjustable preset value and the 
rectifier is delivering more than 10% of its rated current, the rectifier shuts down.  (Adjustable 
from 56 VDC to 59 VDC via the controller.  The restart hysteresis is 0.5 V ±0.2 V.) 

The rectifier then restarts and a HVSD restart timer starts (time value configurable via the 
controller, factory default is 5 minutes).  If output voltage again exceeds the high voltage 
shutdown value before the HVSD restart timer expires, the rectifier shuts down and locks out.  
Manual restart is then required (by turning power to the rectifier off or by removing the rectifier, 
waiting until the LEDs on the rectifier extinguish, then turning power to the rectifier on or re-
inserting the rectifier).  If the rectifier does not experience a high voltage condition before the 
HVSD restart timer expires, the restart circuit is reset. 

If two or more rectifiers are paralleled, only the rectifier causing the high voltage condition shuts 
down. 

2.

 

Backup:  If rectifier output voltage exceeds 59.5 V ±0.5 V (non-adjustable) and the rectifier is 
delivering more than 10% of its rated current, the rectifier shuts down.  The rectifier then 
restarts and a HVSD restart timer starts (time value configurable via the controller, factory 
default is 5 minutes).  If output voltage again exceeds the high voltage shutdown value before 
the HVSD restart timer expires, the rectifier shuts down and locks out.  Manual restart is then 
required (by turning power to the rectifier off or by removing the rectifier, waiting until the LEDs 
on the rectifier extinguish, then turning power to the rectifier on or re-inserting the rectifier). 

 

Over-Temperature Protection:  The rectifier provides over temperature protection by derating output 
power and recovers automatically. 

 

Active Load Sharing:  The rectifier uses advanced digital active load sharing technology.  The output 
current of each rectifier is <±1.2 A of the average current of all rectifiers from 10% to 100% load. 

 

Hot Swappable:  The rectifier is designed to be plug-and-play.  The rectifier can be inserted or removed 
from a live DC power system with no damage.  When the rectifier is plugged into the system, the system 
output voltage will not be affected. 

Содержание NetSure R48-2000

Страница 1: ...NetSure Rectifier Module User Manual UM1R482000e 11BU1360YY Revision J Specification Number 1R482000 1R482000e 1R482000H Model Number R48 2000 R48 2000e R48 2000H...

Страница 2: ...nd materials to be used in performing procedures not specifically described in this document This document may contain confidential and or proprietary information of Vertiv Group Corporation and its r...

Страница 3: ...Overview 7 Specifications 7 DC Output Ratings 7 AC Input Ratings 11 Environmental Ratings 19 Compliance Information 20 Standard Features 20 Mechanical Specifications 23 Operation 24 AC Input Protectio...

Страница 4: ...avoided ANSI OSHA This admonition is not used for situations that pose a risk only to equipment data or service even if such use appears to be permitted in some of the applicable standards OSHA ALERT...

Страница 5: ...pable of producing fatal electrical shock DC Output and Battery Voltages DANGER This system produces DC power and may have a battery source connected to it Although the DC voltage is not hazardously h...

Страница 6: ...ary Read and follow wrist strap manufacturer s instructions outlining use of a specific wrist strap 3 Do not touch traces or components on equipment containing static sensitive components Handle equip...

Страница 7: ...Mode unless load increases to the point where the product of load current and output voltage is approximately 2000W Constant Power Mode As load increases above approximately 2000W non adjustable outpu...

Страница 8: ...varies with changes in input voltage and output voltage It uses an advanced power limitation method The lower input threshold is 85 VAC The rectifier can provide its maximum rated power 2000W as long...

Страница 9: ...00 and R48 2000H or 55 C 131 F R48 2000e the rectifier will not shut down Rather the rectifier limits its maximum output power to maintain the temperature of the power conversion circuit within design...

Страница 10: ...2000 and R48 2000H or 55 C 131 F R48 2000e and 80 C 176 F will result in output power decrease Operation above 80 C 176 F is considered abnormal and should be used on a temporary1 basis only 1 Tempora...

Страница 11: ...ut and 20 to 70 of rated load 3 R48 2000 1R482000 and R48 2000H 1R482000H Psophometric noise is 1 mV at 5 to 100 of rated load 4 R48 2000e 1R482000e Psophometric noise is 2 mV typical at 20 to 70 of r...

Страница 12: ...5 1980 5 99 80 94 90 344 98 110 10 32 2149 8 2139 5 99 52 94 58 395 71 120 10 36 2151 8 2147 5 99 80 94 22 423 81 240 0 0 38 106 6 32 5 30 50 110 89 25 2 13 509 3 494 5 97 10 95 37 78 10 50 4 15 996...

Страница 13: ...5 99 85 94 21 424 15 240 0 0 33 74 3 26 0 35 00 88 72 25 2 11 505 1 494 5 97 90 95 42 77 24 50 4 13 991 9 982 0 99 00 96 21 126 91 75 6 15 1474 3 1467 5 99 54 95 97 201 88 100 8 24 1975 3 1970 0 99 73...

Страница 14: ...0 99 94 89 93 766 53 240 0 0 33 77 8 27 7 35 60 94 52 25 2 23 534 1 525 0 98 30 89 70 184 52 50 4 29 1028 8 1026 0 99 73 91 90 283 66 75 6 38 1529 5 1529 0 99 97 91 90 422 83 100 8 58 2055 2 2055 0 99...

Страница 15: ...2 99 96 89 75 780 85 240 0 0 29 65 9 27 41 00 92 13 25 2 22 531 1 525 98 86 89 86 181 62 50 4 29 1028 7 1027 99 83 91 88 284 42 75 6 37 1531 3 1531 99 98 91 85 425 70 100 8 57 2057 2 2057 99 99 91 20...

Страница 16: ...99 96 91 42 645 48 240 0 0 362 86 5 36 5 42 20 124 54 25 2 20 526 5 516 0 98 00 91 47 150 24 50 4 26 1018 4 1015 0 99 67 93 11 238 56 75 6 31 1513 6 1513 0 99 96 93 09 356 94 100 8 46 2029 2 2029 0 9...

Страница 17: ...0 99 97 91 45 642 57 240 0 0 32 75 0 36 0 48 00 122 84 25 2 18 523 3 516 5 98 70 91 36 152 32 50 4 23 1016 2 1014 0 99 78 93 16 236 62 75 6 30 1513 3 1513 0 99 98 93 03 359 86 100 8 46 2026 2 2026 0 9...

Страница 18: ...Vertiv NetSure Rectifier Module User Manual UM1R482000e 11BU1360YY Rev J 18 Figure 7 Efficiency Curve R48 2000e 1R482000e Figure 8 Efficiency Curve R48 2000 1R482000...

Страница 19: ...arth Capable of withstanding surges per ANSI IEEE C 62 41 1980 Category B3 across the input terminals NOTE This level of protection is a widely used standard for telecommunications power equipment As...

Страница 20: ...ltage Mode unless load increases to the point where the product of load current and output voltage is approximately 2000W Constant Power Mode As load increases above approximately 2000W non adjustable...

Страница 21: ...value before the HVSD restart timer expires the rectifier shuts down and locks out Manual restart is then required by turning power to the rectifier off or by removing the rectifier waiting until the...

Страница 22: ...ized by the controller the output voltage is updated to the setting programmed into the controller If communications with an SCU controller is lost rectifier output voltage goes to a default value pro...

Страница 23: ...n Fail Protection Alarms such as Input Voltage Protection Inner DC Bus Voltage Protection High Temperature Protection Thermal Derating AC Derating AC Fail Imbalance Output Current Address Code Date So...

Страница 24: ...iption There are three 3 indicators located on the rectifier s front panel The functions of these indicators are as shown in Table 14 NOTE DC voltage must be present at the rectifier output terminals...

Страница 25: ...internal output fuse open Rectifier addresses contradictory Flashing Fan not operating rectifier module shuts down Installing Rectifiers The rectifier is hot swappable It can be installed with the sy...

Страница 26: ...tation for instructions Figure 11 Installing a Rectifier TROUBLESHOOTING AND REPAIR Troubleshooting Rectifier Current Sharing Imbalance When multiple rectifiers are operating in parallel and the curre...

Страница 27: ...y object that may be blocking the inlet or outlet Ambient temperature too high or rectifier inlet too close to a heat source lower the ambient temperature or relocate the heat source Rectifier in ECO...

Страница 28: ...n the underside of the rectifier This unlocks the rectifier from the shelf Refer to Figure 11 for latch mechanism illustration 3 Slide the rectifier out by pulling forwards 4 Place the replacement rec...

Страница 29: ...the remainder of this procedure 4 On this rectifier remove the front panel by removing the screws securing the front panel to the chassis and by unplugging the fan from the printed circuit card 5 For...

Страница 30: ...Vertiv NetSure Rectifier Module User Manual UM1R482000e 11BU1360YY Rev J 30 Figure 12 Rectifier Fan Replacement...

Страница 31: ...Vertiv NetSure Rectifier Module User Manual UM1R482000e 11BU1360YY Rev J 31 This page is intentionally blank...

Страница 32: ...VertivCo com Vertiv Headquarters 1050 Dearborn Drive Columbus OH 43085 USA UM1R482000e 11BU1360YY RJ 08 17...

Отзывы: