Vertiv
|
200 A Distribution Fuse Panel Assembly Installation & User Manual (UM563317)
|
Rev. B
12
INSTALLING THE DISTRIBUTION FUSE PANEL
The product can be used at +55 °C (+131 °F) with a maximum of 100 A per side / 200 A total with a one (1) inch
space provided above the unit.
The product can be used at +65 °C (+149 °F) with a maximum of 80 A per side / 160 A total without a space
provided above or below the unit.
Securing the Distribution Fuse Panel to a Relay Rack or a Cabinet Equipment Rack
DANGER!
If the distribution fuse panel is mounted in a relay rack, the relay rack must be securely
anchored to the floor before the distribution fuse panel is installed.
NOTE!
Ventilation holes in the distribution fuse panel must not be blocked.
The distribution fuse panel is designed to mount in a standard 19” or 23” relay rack or equipment rack having 1”
or 1-1/4” multiple drillings.
•
Two 19” mounting brackets are furnished (adjustable for flush front mounting or 2”, 4”, or 5” front
projection mounting).
•
Two 23” mounting brackets are furnished (adjustable for flush front mounting or 2”, 4”, or 5” front
projection mounting).
on page 9 for overall dimensions.
Procedure
1.
Attach the furnished 19” or 23” mounting brackets to the distribution fuse panel. Note that bracket
mounting holes are provided on the side of the distribution fuse panel to allow for a flush front mounting
or a 2”, 4”, or 5” front projection mounting. Torque mounting bracket to distribution fuse panel hardware
to 11 in-lbs.
2.
Position the distribution fuse panel in the relay rack or cabinet equipment rack.
3.
Secure the distribution fuse panel to the relay rack or cabinet equipment rack using hardware as shown
in
(see
for recommended torque). Use grounding washers as indicated in
NOTE!
Install (orient) the ground washers so the teeth dig into the mounting angles for a secure
ground connection.
NOTE!
Compliance with Telcordia GR-1089-CORE requires that prior to mounting the system to the
equipment rack:
•
All paint must be removed from the front surface of each equipment rack rail where it mates with a
shelf-mounting bracket, so that good metal-to-metal contact can be established between the shelf
and rack.
•
The shelf-to-rack mating surfaces must be cleaned.
•
Electrical anti-oxidizing compound must be applied to the shelf-to-rack mating surfaces.
Содержание NetSure NSFP200
Страница 24: ...UM563317 RB 05 17...