SAG582120600

 

System Application Guide 

Revision BK, September 27, 2017 

Spec. No. 582120600 (Model 801DB 

NVGB

 

Page 18 of 75 

List 139:  Optional Internal Ground/Return Bar Paralleling Kit, 8-Panel Bay (Panel Length) 

Features 

 

Parallels the 

List 117

 Internal Ground/Return Bars. 

 

Each List 139 consists of two (2) Paralleling Bars for two sides. 

Restrictions 

For use with 

List 117

 only. 

Ordering Notes 

1)

 

Order one (1) List 139 if two (2) List 117 ordered for the same bay.  

 

List 143:  Bay Input Feed and Shunt Assembly (4 Cables, 25 mV. Shunts) 

 

Provides landing points for four (4) input leads (on each side). 

 

Provides an 800A, 25mV shunt (one per side). 

 

Can be rotated for top or bottom feed configurations. 

 

See 

DC Input Connections

 under 

Wiring Illustrations

 in ACCESSORY DESCRIPTIONS for 

input termination specifications. 

Restrictions 

For use in Lists 

106

108

206

 an

208

Ordering Notes 

1)

 

Order as required.  Each List 143 provides input terminations and shunts for both sides. 
For top and bottom feed 2-load applications, order one (1) List 143 and specify top or 
bottom feed. 
For top and bottom feed multi-load applications, order one (1) List 143 for each Side A/Side 
B load and specify top or bottom feed. 

2)

 

Order input lugs as required pe

DC Input Cable Sizes and Lugs Selection

 under 

Wiring 

Notes

 in ACCESSORY DESCRIPTIONS. 

 
 

List 144:  Bay Input Feed and Shunt Assembly (2 Cables, 25 mV. Shunts) 

 

Provides landing points for two (2) input leads (on each side). 

 

Provides an 800A, 25mV shunt (both sides). 

 

Can be rotated for top or bottom feed configurations. 

 

See 

DC Input Connections

 under 

Wiring Illustrations

 in ACCESSORY DESCRIPTIONS for 

input termination specifications. 

Restrictions 

For use in Lists 

106

108

206

 an

208

Ordering Notes 

1)

 

Order as required.  Each List 144 provides input terminations and shunts for both sides. 
For top and bottom feed 2-load applications, order one (1) List 144 and specify top or 
bottom feed. 
For top and bottom feed multi-load applications, order one (1) List 144 for each Side 
A/Side B load and specify top or bottom feed. 

2)

 

Order input lugs as required pe

DC Input Cable Sizes and Lugs Selection

 under 

Wiring 

Notes

 in ACCESSORY DESCRIPTIONS. 

Home

 

Содержание NetSure 801DB NVGB

Страница 1: ...asily be configurable for top or bottom feed Each bay is equipped with a digital meter assembly The List 105 and 107 bays provide a basic digital meter which is capable of displaying system load volta...

Страница 2: ...SAG582120600 System Application Guide Revision BK September 27 2017 Spec No 582120600 Model 801DB NVGB Page 2 of 75 Home...

Страница 3: ...Bay Input Feed and Shunt Assembly 2 Cables 50 mV Shunts 19 List 147 Bay Input Feed and Shunt Assembly 4 Cables 50 mV Shunts 19 List 148 2400A Ground Return Input Assembly with Optional Bonding Strap...

Страница 4: ...ed in Bay s Top Center 64 Replacement Alarm Reference and Control Fuses List 106 and 108 Bays 64 Fuses Located on Auxiliary Fuse Card at Top of Bay 64 Replacement Circuit Cards List 105 and 107 Bays 6...

Страница 5: ...or Blank Panel List 118 Distribution Panel A List 110 or 115 or Blank Panel List 118 Paralleling Bar List 130 Paralleling Bar List 130 Paralleling Bar List 130 Paralleling Bar List 130 Distribution Pa...

Страница 6: ...Ground Return Bar Paralleling Kit List 148 2400A Ground Return Input Assembly with Optional Bonding Strap for List 116 Ground Return Bar List 150 Optional Capacitor Precharge Assembly List 151 Dressin...

Страница 7: ...or 125 or Blank Panel List 128 Distribution Panel E List 120 or 125 or Blank Panel List 128 Distribution Panel F List 120 or 125 or Blank Panel List 128 Distribution Panel C List 120 or 125 or Blank...

Страница 8: ...148 2400A Ground Return Input Assembly with Optional Bonding Strap for List 126 Ground Return Bar List 150 Optional Capacitor Precharge Assembly List 151 Dressing Bar List 153 Load Distribution Cable...

Страница 9: ...nd specify top or bottom feed List 120 Only For 3 load side by side applications order three 3 List 143 or 144 and order three 3 556103 List 125 Only For 3 load side by side applications order three 3...

Страница 10: ...A Side B load and specify top or bottom feed List 120 Only For 3 load side by side applications order three 3 List 143 or 144 and order three 3 556103 List 125 Only For 3 load side by side application...

Страница 11: ...143 or 144 and order four 4 556103 For top and bottom feed 2 load side by side applications order two 2 List 143 or 144 two 2 556103 and two 2 List 130 List 115 Only For 4 load side by side applicatio...

Страница 12: ...ations order four 4 List 143 or 144 and order four 4 556103 For top and bottom feed 2 load side by side applications order two 2 List 143 or 144 two 2 556103 and two 2 List 130 List 115 Only For 4 loa...

Страница 13: ...as required per Distribution Devices and Lug Selection in ACCESSORY DESCRIPTIONS 4 Replacement panels will be equipped with 12 TLS TPS Fuseholders TPL fuseholders P N 516241 may be ordered to field mo...

Страница 14: ...ces a Distribution Panel on the left and right side with a panel length internal ground return bar Consists of two 2 ground return bar assemblies and two 2 blank cover panels For installation in top f...

Страница 15: ...Connections under Wiring Illustrations in ACCESSORY DESCRIPTIONS for load termination specifications Restrictions 640A maximum continuous For use in List 106 or List 206 only Ordering Notes 1 Order a...

Страница 16: ...VSS Device s as required per Transient Voltage Surge Suppressor TVSS Device in ACCESSORY DESCRIPTIONS List 126 Optional Internal Ground Return Bar 6 Panel Bay Full Bay Length Features Provides two ful...

Страница 17: ...se positions See Load Distribution Connections under Wiring Illustrations in ACCESSORY DESCRIPTIONS for load termination specifications Restrictions For use in List 106 or List 206 only Ordering Notes...

Страница 18: ...ed 2 load applications order one 1 List 143 and specify top or bottom feed For top and bottom feed multi load applications order one 1 List 143 for each Side A Side B load and specify top or bottom fe...

Страница 19: ...B load and specify top or bottom feed 2 Order input lugs as required per DC Input Cable Sizes and Lugs Selection under Wiring Notes in ACCESSORY DESCRIPTIONS List 147 Bay Input Feed and Shunt Assembl...

Страница 20: ...is available to increase that capacity to 2400 Amps and provide additional cable landing points Each bay can accommodate 1 List 148 List 148 offers cable termination at the rear of the bay and the opt...

Страница 21: ...ordered when using the two foot 2 extension Maximum of six 6 additional dressing bars to be ordered when using the four and one half foot 4 1 2 extension List 251 Dressing Bar Features Provides adjus...

Страница 22: ...option Restrictions Upgrades List 107 only Original 50mV load shunts must be replaced with 25mV shunts Six 6 25mV shunts P N 545619 are included in List 166 Ordering Notes 1 Order one 1 List 166 to up...

Страница 23: ...ernal sense option and an Ethernet connection requires List 170 Ethernet option Restrictions Upgrades List 105 only Original 50mV load shunts must be replaced with 25mV shunts Eight 8 25mV shunts P N...

Страница 24: ...MODEL 1293V3 Distribution Bus Modules List Number Part Number Description 8 Panel Bay TLS TPS Type Fuseholders 3 70A e w Internal Grounding 20G 58212060020G 6 Panel Bay 15 58212060015 8 Panel Bay Bull...

Страница 25: ...r 24 20 21 22 or 24 31 36 15 15 35 or 37 25 25 36 or 38 10 11 12 14 or 15 10 11 12 14 or 15 35 or 37 13 13 35 or 37 20 20G 21 22 24 or 25 20 20G 21 22 24 or 25 36 or 38 23 23 36 or 38 15 10 11 12 14 o...

Страница 26: ...0 N A 115 1 N A 116 8 N A 120 N A 0 125 N A 1 126 N A 6 Side by Side Busbar Link Kit for Use with List 110 and List 120 P N 556103 Features Connects each side of a List 143 or List 144 together side b...

Страница 27: ...List 110 and List 120 556103 582120600 List 144 List 143 Similar when used with List 115 and List 125 557256 Hardware Build Up 3 8 16 x 1 1 4 Bolt 3 8 Flat Washer Busbar Link 3 8 Flat Washer 3 8 Lock...

Страница 28: ...100 and six 6 1 4 20 hex nuts P N 228557100 Part No 556378 provides one 1 busbar P N 555919 six 6 1 4 flat washers P N 214110100 six 6 1 4 split lock washers P N 215111100 and six 6 1 4 20 hex nuts P...

Страница 29: ...Kit 534834 Ordering Notes 1 Order Return Ground Bar Assembly s as required One 1 per bay provides landing positions for each fuse position in the bay assuming that cables are terminated back to back I...

Страница 30: ...st 125 Distribution Panel Restrictions To be used with Distribution Panels List 115 and List 125 only All unparalleled Distribution Panels require a TVSS Device only one 1 TVSS Device required per par...

Страница 31: ...S TPS and TPL fuseblocks List 110 includes 12 TLS TPS Fuseblocks P N 248817100 and List 120 includes 20 TLS TPS Fuseblocks P N 248817100 For panels factory configured in a bay each TPL Fuseblock P N 5...

Страница 32: ...S 50 TLS050 60 248234200 TPS 60 TLS060 70 248234500 TPS 70 TLS070 Each fuse requires 1 Fuseblock P N 248817100 See Ordering Notes in this section For each fuseblock ordered also order 1 P N 248610301...

Страница 33: ...se Fuse Installed in Open Fuse Case Fuse Installed in Closed Fuse Case Lists 110 and 120 TPL Fuseblock 5 16 18 swage studs for installation of customer provided single hole lugs Max Lug Width 1 8 Max...

Страница 34: ...Ordering Notes in this section Fuseblock P N 516241 also includes 1 P N 248610301 alarm fuse GMT 18 100A and 1 P N 248898700 safety fuse cover GMT X See Table 9 for recommended load distribution wire...

Страница 35: ...ovides a GMT A alarm type fuse which operates open to provide an alarm indication if the distribution fuse opens Restrictions The circuit breakers fuses and fuseblocks specified in this section are fo...

Страница 36: ...Toggle Handle Bullet Nose Circuit Breaker Bullet Nose Fuseholder P N 117201 includes Fuseholder Alarm Fuse and Alarm Fuse Safety Cover Alarm Fuse Replacement P N 248610301 Safety Fuse Cover Replacemen...

Страница 37: ...70 1 102284 101608 75 1 102285 101609 80 1 121996 121995 90 1 138887 138888 100 1 102286 101610 125 2 516991 516838 Use lugs in Table 7 Special Crimp Lug 150 see Caution below 2 516993 516839 175 see...

Страница 38: ...PS 6 TLS006 10 248231500 TPS 10 TLS010 15 248231800 TPS 15 TLS015 20 248232100 TPS 20 TLS020 25 248232400 TPS 25 TLS025 30 248232700 TPS 30 TLS030 40 248233300 TPS 40 TLS040 50 248233900 TPS 50 TLS050...

Страница 39: ...5349900 4 AWG 245350000 2 AWG 245348200 1 0 AWG 245347100 2 0 AWG 245347200 3 0 AWG 245347300 4 0 AWG 245347400 250 kcmil 245347500 300 kcmil 245347600 350 kcmil 245347700 400 kcmil 245347800 500 kcmi...

Страница 40: ...odel 801DB NVGB Page 40 of 75 Special Lugs and Adapters Referenced in Table 7 Special Lug See Table 7 for Part Numbers Special Adapter P N 545346 Special Lug and Adapter 3 Pole Lug Adapter Kit P N 547...

Страница 41: ...Notes 1 Order as required P N 544201 Two 2 Foot Box Framework Extension Features The 2 Foot Box Framework Extension allows a standard 7 foot box framework to extend to 9 feet Restrictions For use in...

Страница 42: ...ring List 106 206 108 and 208 Bays Input Output Circuit Card Features An input output circuit card is located behind the top left panel in each bay This circuit card provides four alarm relays each wi...

Страница 43: ...SSORY DESCRIPTIONS Restrictions The rating of the distribution device determines the wire size requirements Refer to the American National Standards Institute ANSI approved National Fire Protection As...

Страница 44: ...nstitute ANSI approved National Fire Protection Association s NFPA National Electrical Code NEC Table 310 16 for copper wire at 90 C conductor temperature operating in ambients of 30 C and 40 C was us...

Страница 45: ...ion s NFPA National Electrical Code NEC Table 310 16 for copper wire at 90 C conductor temperature operating in ambients of 30 C and 40 C was used For other operating ambient temperatures refer to the...

Страница 46: ...ode NEC Table 310 16 for copper wire at 90 C conductor temperature operating in ambients of 30 C and 40 C was used For other operating ambient temperatures refer to the National Electrical Code For op...

Страница 47: ...Note that loads typically should not exceed 80 of capacity therefore input cables have been sized for an overcurrent protection device rated at 800A When making connections observe correct polarity Ex...

Страница 48: ...SAG582120600 System Application Guide Revision BK September 27 2017 Spec No 582120600 Model 801DB NVGB Page 48 of 75 Wiring Illustrations Overall Installer s Connections Home...

Страница 49: ...System Application Guide SAG582120600 Spec No 582120600 Model 801DB NVGB Revision BK September 27 2017 Page 49 of 75 Bay Frame Grounding Connection Home...

Страница 50: ...SAG582120600 System Application Guide Revision BK September 27 2017 Spec No 582120600 Model 801DB NVGB Page 50 of 75 External Alarm and Meter Alarm Card Input Connections Home...

Страница 51: ...s as ordered Connect faston connector end of Internal Fuse Kit to one of these lugs Input Feed and Shunt Assembly 48V Input B Feed for digital meter and alarm circuit card power input Connect to an ex...

Страница 52: ...SAG582120600 System Application Guide Revision BK September 27 2017 Spec No 582120600 Model 801DB NVGB Page 52 of 75 Home...

Страница 53: ...System Application Guide SAG582120600 Spec No 582120600 Model 801DB NVGB Revision BK September 27 2017 Page 53 of 75 Home...

Страница 54: ...SAG582120600 System Application Guide Revision BK September 27 2017 Spec No 582120600 Model 801DB NVGB Page 54 of 75 Home...

Страница 55: ...rovided External Busbar 48V Load Connections Load Return Connections to Optional Internal Ground Return Busbar or Customer Provided External Busbar Optional Internal Ground Return Busbar Bay Length sh...

Страница 56: ...tions Rear View wired from the rear of the bay 1 4 20 studs on 5 8 centers for installation of customer provided two hole lugs Torque to 72 in lbs Maximum Lug Width is 0 610 Maximum Wire Size is 2 AWG...

Страница 57: ...System Application Guide SAG582120600 Spec No 582120600 Model 801DB NVGB Revision BK September 27 2017 Page 57 of 75 Home...

Страница 58: ...ons Front View 8 Panel Bay Front View 6 Panel Bay Optional List 127 Ground Bar Assembly Each List 127 provides two 2 Ground Bar Assemblies Optional List 117 Ground Bar Assembly Each List 117 provides...

Страница 59: ...und Bar 8 Panel Bay List 127 Ground Bar 6 Panel Bay 1 4 clearance holes slots on 5 8 centers for installation of customer provided two hole lugs Torque to 72 in lbs Maximum Lug Width is 0 610 Maximum...

Страница 60: ...Page 60 of 75 Internal Ground Bar Assembly P O List 117 Paralleling Bar List 139 Hardware Build Up 3 8 16 x 1 1 4 Bolt 3 8 Belleville Lock Washer 3 8 Flat Washer Internal Ground Bar Assembly Paralleli...

Страница 61: ...nd Shunt Assembly Addtional Input Feed and Shunt Assemblies are installed on any Distribution Panel not paralleled with a Distribution Panel that has an Input Feed and Shunt Assembly installed List 14...

Страница 62: ...to 180 in lbs Max lug width is 2 00 Max wire size is 750 kcmil List 148 Feed Optional bonding strap P O List 148 can be removed if not required Optional bonding strap P O List 148 can be removed if no...

Страница 63: ...installation of customer provided two hole lugs Torque to 180 in lbs Maximum Lug Width is 2 00 Maximum Wire Size is 4 0 AWG Top Feed Installations Bottom Feed DC Input Connections Battery Return Leads...

Страница 64: ...l Meter and Alarm Circuit Card Feed B 48V Input Safety Fuse Cover Bussmann GMT X 248898700 Table 11 Replaceable Alarm Reference and Control Fuses List 106 and 107 Bays Replacement Alarm Reference and...

Страница 65: ...75 Replacement Circuit Cards List 105 and 107 Bays Ordering Notes 1 Refer to the following table Item P N External Alarm Circuit Card 486339800 Replacement Circuit Cards List 106 108 206 and 208 Bays...

Страница 66: ...bution Center for Communications Equipment 1 3 2 NEBS Compliance Compliance verified by a Nationally Recognized Testing Laboratory NRTL per GR 1089 CORE and GR 63 CORE Contact Vertiv for NEBS complian...

Страница 67: ...Page Access Levels User configurations provide a Page Access Level which can be used to limit the functions available to a particular user Eight Page Access Levels are available E PC Requirements 1 W...

Страница 68: ...ec No 582120600 Model 801DB NVGB Page 68 of 75 MECHANICAL SPECIFICATIONS LIST 106 AND 108 Floor Hole Drilling Pattern Dimensions Front 3 8 16 Welded Nut 4 0 750 Dia 8 PLACES 2 275 1 275 1 875 26 000 2...

Страница 69: ...stem Application Guide SAG582120600 Spec No 582120600 Model 801DB NVGB Revision BK September 27 2017 Page 69 of 75 MECHANICAL SPECIFICATIONS LIST 206 AND 208 Floor Hole Drilling Pattern Dimensions Hom...

Страница 70: ...SAG582120600 System Application Guide Revision BK September 27 2017 Spec No 582120600 Model 801DB NVGB Page 70 of 75 Dimensions List 108 8 Bus Bay Home...

Страница 71: ...System Application Guide SAG582120600 Spec No 582120600 Model 801DB NVGB Revision BK September 27 2017 Page 71 of 75 Dimensions List 208 8 Bus Bay Home...

Страница 72: ...SAG582120600 System Application Guide Revision BK September 27 2017 Spec No 582120600 Model 801DB NVGB Page 72 of 75 Dimensions List 106 6 Bus Bay Home...

Страница 73: ...System Application Guide SAG582120600 Spec No 582120600 Model 801DB NVGB Revision BK September 27 2017 Page 73 of 75 Dimensions List 206 6 Bus Bay Home...

Страница 74: ...ber 27 2017 Spec No 582120600 Model 801DB NVGB Page 74 of 75 RELATED DOCUMENTATION Schematic Diagram SD582120600 Power System Wiring Diagram T582120600 Power System Instructions Section 5674 Power Sys...

Страница 75: ...8 bay schematics 02 20 2015 Mitchelle Emata BJ LLP223817 Rebranded Vertiv 04 25 2017 John Jasko BK LLP224352 Document converted to latest Vertiv format 09 27 2017 John Jasko Home VertivCo com Vertiv...

Отзывы: