Page 16 of 75
List 125: Distribution Panel, 6-Panel Bay
Features
♦
Twenty-Eight (28) bullet nose circuit breaker and/or TLS/TPS fuse (with bullet nose
fuseholder) positions.
♦
See
under
Wiring Illustrations
in ACCESSORY DESCRIPTIONS
for load termination specifications.
Restrictions
640A maximum continuous.
For use in
only.
Caution: Circuit breaker with a 150 ampere or greater rating SHALL HAVE an empty
mounting position between it and any other overcurrent protective device.
Ordering Notes
1)
Order as required.
2)
Specify mounting location for each Distribution Panel per bay. This instructs the factory
where to mount each Distribution Panel when the bay is populated with different types of
Distribution Panels.
3)
Order distribution fuses, fuseholders, circuit breakers, and load lugs as required per
Distribution Devices and Lug Selection
in ACCESSORY DESCRIPTIONS.
4)
Order TVSS Device(s) as required per
Transient Voltage Surge Suppressor (TVSS) Device
DESCRIPTIONS.
List 126: Optional Internal Ground/Return Bar, 6-Panel Bay (Full Bay Length)
Features
♦
Provides two full bay length internal ground/return bars (one per side).
♦
See
under
Wiring Illustrations
in ACCESSORY DESCRIPTIONS for load
termination specifications.
♦
Includes two (2) Input Lug Landing Plate Assemblies (one per side).
♦
Can be configured for top or bottom feed.
Restrictions
only.
Ordering Notes
1)
Order as required.
2)
Specify mounting location of included Input Lug Landing Plate Assemblies: top for top-feed or bottom
for bottom feed.
3)
List 126 internal ground/return bars are rated for 1200 Amps. List
is available to increase that
capacity to 2400 Amps and provide additional cable landing points. Each bay can accommodate (1) list
148. List 148 offers cable termination at the rear of the bay and the option of a bonding strap.
Mounting location (top or bottom) of List 148 will be opposite that specified for the Input Lug Landing
Plate Assemblies of List 126.
4)
Order load lugs as required per
Distribution Devices and Lug Selection
in ACCESSORY DESCRIPTIONS.