Vertiv | Liebert PEX4 | User Manual
48
Installation
2.8. Electrical Installation
In this section, the electrical installation of the PEX4 unit is explained in-depth, which include the installation
considerations, indoor wiring, power lines connection to the outdoor unit, and the checklist.
2.8.1. Installation Notes
• The connection of all power cables, control cables, and ground cables should comply with the local and
national electrical regulations. Parts of the equipment suitable for outdoor use should not be lighter than the
normal PVC sheathed cord GB5023.1 (IDT IEC60277). In outdoor use, the power cord should not be lighter
than neoprene armored cords (line 57 in IEC 60245).
•
The electrical installation and maintenance must be performed by authorized professional/installation
personnel.
•
See the unit name-plate for the full load current. The cable sizes should meet the local wiring rules.
• Mains supply requirement:
380V t
o
415 V, 3 Ph+N
~
50 Hz/ 60 Hz
.
• If the soft power cable uses Y-connection, and if the cable is damaged, it must be replaced by professional
service personnel.
•
Before the wiring, use a volt-meter to measure the power supply voltage and ensure that the power supply
has been switched off.
•
The applicable grid for this air conditioner: TN, TT star connection power system; consult Vertiv local
representative for other connections.
• A breaking device must be provided to be disconnected from power supply.
• Install suitable RCD according to actual installation
.
2.8.2. Wiring of Indoor Unit
• Locating electrical ports of indoor unit
Locations of the low voltage devices are visible after the front door of the electrical control box of the indoor
unit is opened, as shown in
. The distribution information of the detailed low voltage components are
differentiated according to the labels.