2.2.6. System Installation Mode
The system installation schematic diagram explains the process of installation for the condenser.
No.
Description
No.
Description
1
Inverted traps (higher than the highest copper
pipe of condenser)
8
Humidifier supply pipe
2
Outdoor unit
9
Raised floor
3
Sealed
10
Indoor unit
4
Supporting bars
11
Discharge pipe slope
5
Thermal isolated layer under floor
12
Oil trap (Oil storage bend)
6
Floor
13
Liquid pipe (avoid direct sunlight)
7
Condensate drain pipe
Figure 2-9 Condenser is Placed Higher than the Compressors during Installation
If the condenser is installed higher than the compressor (see
), a back-bend should be fitted to the
discharge line and liquid line of the condenser, so as to prevent the liquid refrigerant from flowing back when
the condenser stops. The top end of the inverted back-bend should be installed higher than the ultimate level
of the copper pipe of the condenser. However, if the condenser is installed lower than the compressor, then
there is no need of modification.