Vertiv | Liebert PEX+Chilled Water | User Manual
50
iCOM Controller Operation
The indicators are described in
. The functions of the buttons are described in
.
Table 4-1 Indicator Description
Indicator
Description
Alarm indicator
The alarm indicator turns on red upon alarms triggered. It is off after the alarm has been cleared
Operation indicator The operation indicator turns on green when the unit is operating. When the unit is shut down,
the indicator is yellow
Table 4-2 Button Description
Button
Function Description
ON/OFF
button
• Switch on/ off the system. Press the ON/ OFF button to shut down the unit, or to start an idle system.
• Test the display state of the back-light of the LCD and operation indicator.
• After powering-on, when the system is stand-by (defined as test state in this manual), press the ON/
OFF button to turn on the unit, the indicator turns to green, and the LCD back-light turns on.
This is for testing whether the LCD back-light and operation indicator are normal.
Enter
button
• Enter the selected menu or save the setting after parameters are changed. Select the menu or
parameter by pressing the direction button, the menu and the parameter is high-lighted.
• Test the display of characters.
• When the system is in the test state, press the Enter button that will display the ASCII code. This
function is used to test whether the characters are displayed normally on the LCD.
ESC
button
• Quit the current menu.
• Cancel the current change of parameters.
• Test the LCD high light.
• Press the ESC button to switch the LCD between light and high light when the system is in the test
state. This function can test whether the LCD high light is normal.
Up button
• Increase the value of the displayed parameters during parameter setting.
• Scroll a row or a screen up in the query state.
• Test the buzzer.
• Press the Up button when the system is in the test state to increase the buzzing frequency (initial
value: 0%). Meanwhile the buzzer will sound at the set frequency. This function is used to test whether
the buzzer is normal.
Down
button
• Decrease the value of the displayed parameters during parameter setting.
• Scroll a row or a screen down in the query state.
• Test the buzzer.
• If the buzzer frequency is not 0%, press the down button to decrease the buzzing frequency when the
system is in the test state. Meanwhile the buzzer will sound at the set frequency. This function is used
to test whether the buzzer is normal.