Line Size, O.D., in.
R-407C, lb/100 ft. (kg/30m)
Liquid Line
Suction Line
3/8
3.7 (1.7)
—
1/2
6.9 (3.1)
—
5/8
11.0 (5.0
0.4 (0.2)
3/4
15.7 (7.1)
0.6 (0.3)
7/8
23.0 (10.4)
1.0 (0.4)
1-1/8
—
1.7 (0.7)
1-3/8
—
2.7 (1.1)
Table 10.4 Line charges - refrigerant
per 100 ft. (30m) of Type L copper tube
Line Size, in.
Length, ft. (m)
Charge R-407C, oz (kg)
3/8 liquid
15 (4.5)
5 (0.14)
30 (9)
10 (0.28)
5/8 or 7/8 suction
15 (4.5)
5 (0.14)
30 (9)
10 (0.28)
Table 10.5 Refrigerant charge in Liebert pre-
charged R-407C line sets
Copper Pipe OD,
in.
90 Degree Elbow
Copper
90 Degree Elbow
Cast
45 Degree
Elbow
Tee
Gate
Valve
Globe
Valve
Angle
Valve
1/2
0.8 (0.24)
1.3 (0.39)
0.4 (0.12)
2.5
(0.76)
0.26 (0.07)
7.0 (2.13)
4.0 (1.21)
5/8
0.9 (0.27)
1.4 (0.42)
0.5 (0.15)
2.5
(0.76)
0.28 (0.08)
9.5 (2.89)
5.0 (1.52)
3/4
1.0 (0.3)
1.5 (0.45)
0.6 (0.18)
2.5
(0.76)
0.3 (0.09)
12.0 (3.65)
6.5 (1.98)
7/8
1.45 (0.44)
1.8 (0.54)
0.8 (0.24)
3.6
(1.09)
0.36 (0.1)
17.2 (5.24)
9.5 (2.89)
1-1/8
1.85 (0.56)
2.2 (0.67)
1.0 (0.3)
4.6 (1.4)
0.48 (0.14)
22.5 (6.85)
12.0 (3.65)
1-3/8
2.4 (0.73)
2.9 (0.88)
1.3 (0.39)
6.4
(1.95)
0.65 (0.19)
32.0 (9.75)
16.0 (4.87)
1-5/8
2.9 (0.88)
3.5 (1.06)
1.6 (0.48)
7.2
(2.19)
0.72 (0.21)
36.0 (10.97)
19.5 (5.94)
Refrigerant trap = Four times equivalent length of pipe per this table.
Table 10.6 Equivalent lengths for various pipe fittings, ft (m)
Vertiv
| Liebert Mini-Mate2—2 and 3 ton Technical Data Manual |
60
Содержание Liebert Mini-Mate2
Страница 4: ...Vertiv Liebert Mini Mate2 2 and 3 ton TechnicalDataManual 4...
Страница 12: ...Vertiv Liebert Mini Mate2 2 and 3 ton TechnicalDataManual 12 This page intentionally left blank...
Страница 16: ...Vertiv Liebert Mini Mate2 2 and 3 ton TechnicalDataManual 16 This page intentionally left blank...
Страница 28: ...Vertiv Liebert Mini Mate2 2 and 3 ton TechnicalDataManual 28 This page intentionally left blank...
Страница 44: ...Vertiv Liebert Mini Mate2 2 and 3 ton TechnicalDataManual 44 This page intentionally left blank...
Страница 58: ...Vertiv Liebert Mini Mate2 2 and 3 ton TechnicalDataManual 58 This page intentionally left blank...
Страница 61: ...Figure 10 1 Refrigerant piping diagram Vertiv Liebert Mini Mate2 2 and 3 ton TechnicalDataManual 61...
Страница 62: ...Vertiv Liebert Mini Mate2 2 and 3 ton TechnicalDataManual 62 This page intentionally left blank...
Страница 64: ...Vertiv Liebert Mini Mate2 2 and 3 ton TechnicalDataManual 64 This page intentionally left blank...
Страница 68: ...Vertiv Liebert Mini Mate2 2 and 3 ton TechnicalDataManual 68 This page intentionally left blank...
Страница 70: ...Vertiv Liebert Mini Mate2 2 and 3 ton TechnicalDataManual 70 This page intentionally left blank...
Страница 81: ......