Enable
Enables/disables notification. Touch the switch to set On or Off.
•
When disabled, events are not logged or displayed and visual/audible alarm notifications are not made.
Type
Logging and notification level of the event. Table 4.1 below, describes the event type and notification it generates.
Table 4.2 below, lists the default types for events.
Type
Description
Message
Stored in event log only. No visual or audible notification.
Warning
Listed with a yellow status dot on the ALARMS panel and the LED flashes.
See Table 11.1 on page 95, and
Alarm
Listed with a red status dot on the ALARMS panel, the LED flashes, and the audible alarm sounds.
See Table 11.1 on page 95,
on page 14, and
Enabling the Audible Alarm Notification
Table 4.1 Notification Types
Table 4.2 below lists the default settings for each event.
•
Internal delay is factory set and not adjustable. It is the time delay after event trigger that notification is sent.
•
Default delay may or may not be adjustable and is added to the internal delay of event notification.
•
Type may be adjustable or may be fixed.
NOTE: Depending on customization, some events may not be available on your cooling unit.
Event
Internal Delay
Default Delay/Range
for Adjustment
Type
MAIN FAN OVERLOAD
2 sec
5 sec/0 – 9999 *
ALM
LOSS OF AIRFLOW
3 sec
3 sec/0 – 9999 *
ALM
CLOGGED FILTERS
2 sec
2 sec/0 – 9999 *
WRN
HIGH ROOM TEMP
1 min. after fan on
30 sec/0 – 9999
Fixed to WRN
LOW ROOM TEMP
1 min. after fan on
30 sec/0 – 9999
Fixed to WRN
HIGH ROOM HUM
1 min. after fan on
30 sec/0 – 9999
Fixed to WRN
LOW ROOM HUM
1 min. after fan on
30 sec/0 – 9999
Fixed to WRN
HIGH TEMP SENSOR A
1 min. after fan on
30 sec/0 – 9999
Fixed to WRN
LOW TEMP SENSOR A
1 min. after fan on
30 sec/0 – 9999
Fixed to WRN
HIGH HUM SENSOR A
1 min. after fan on
30 sec/0 – 9999
Fixed to WRN
LOW HUM SENSOR A
1 min. after fan on
30 sec/0 – 9999
Fixed to WRN
COMP 1 OVERLOAD
Internal Calc.
no
ALM
COMP 2 OVERLOAD
Internal Calc.
no
ALM
COMP 1 HIGH PRESSURE
Internal Calc.
no
ALM
Table 4.2 Event Notification Defaults
Vertiv™ | Liebert® iCOM™ Installer/User Guide
46
Содержание Liebert iCOM DP400/500
Страница 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Страница 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Страница 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Страница 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Страница 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Страница 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Страница 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Страница 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...
Страница 179: ...Vertiv Liebert iCOM Installer User Guide...