11 PERFORMING DIAGNOSTICS
NOTE: Depending on the type of thermal management unit, included components, and control settings of your
system, all of the options listed may not be available on your iCOM display.
NOTE: Your Liebert® DSE™ Packaged Solution does not offer humidification or dehumidification functions. Please
disregard those settings/fields when mentioned in this guide or displayed on the iCOM controller.
11.1 Cooling Unit Status LED
Just below the iCOM touchscreen display is an LED that changes color and flashes on-off indicating cooling unit status. See
Table 11.1 below, for the LED colors and meanings.
State
Color(s)
Meaning
Solid
Green
Powered on and operating.
Solid
Amber
In diagnostic/service mode or powered off.
Solid
Red
Active warning or alarm present and acknowledged.
Flashing
Amber/Green
In sleep or U2U standby mode and available to operate.
Flashing
Red/Green
Operating with an active warning or alarm.
Flashing
Amber/Red
Shut down (not operating) because of an unacknowledged alarm.
Flashing
Red
Active warning or alarm present but unacknowledged.
Flashing
Blue
iCOM display is starting-up or updating iCOM firmware.
Table 11.1 Cooling Unit LED Colors and State Meanings
11.2 Enabling Manual Mode for Diagnostics
Use manual mode to test components, validate operation, and evaluate performance.
NOTE: When manual mode is enabled, the cooling unit does not operate normally:
•
Fan operation depends on the diagnostic category in use.
•
Safety routines will prevent the use of some diagnostic features.
•
Active alarms may prevent some the use of some diagnostic functions.
•
In most cases, all components are turned-off.
NOTE: When manual mode is disabled, all components and the cooling unit return to normal operation. See
on the next page. Manual mode times-out after 30 minutes of inactivity and normal
operation resumes.
1.
Touch
, then
>
Diagnostic/Service
>
Diagnostics
>
Manual Mode
in the Category list.
The MANUAL MODE panel displays.
2.
Touch the
Enable
check box in the upper-right of the
MANUAL MODE
panel.
The MANUAL MODE confirmation dialog opens.
3.
Touch
OK
to enable manual mode.
Enable is checked and manual control for diagnostics enabled.
•
Touch
Cancel
to close the dialog and manual mode remains disabled.
11 Performing Diagnostics
95
Содержание Liebert iCOM DP400/500
Страница 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Страница 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Страница 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Страница 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Страница 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Страница 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Страница 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Страница 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...
Страница 179: ...Vertiv Liebert iCOM Installer User Guide...