Battery Cabinet User Manual |
36
Table 13
Battery cabinet system—UPS and Liebert EXM Battery Cabinet
UPS Rating,
kVA
Battery
Cabinet
Breaker
Maximum
Battery Current,
A
Battery
Cabinet Size,
mm
Copper
Wire
Compression
Lug
Bolt
Size
10-40
225A
187
600, 880
(1) 250kcmil
54868BE (2
Hole)
1/2"
10-40
225A
187
320
(1) 250kcmil
54174 (1 Hole)
3/8"
60-120
555A
560
600, 880
(2)
400kcmil
54874BE (2
Hole)
1/2"
140-200 *
555A
560
600, 880
(2)
400kcmil
54874BE (2
Hole)
1/2"
* 140-200kVA UPS requires a minimum of two cabinets.