8.1 Service/Maintenance Access to the Evaporator Compartment
The evaporator section includes access doors that swing inward on both sides to allow access for
maintenance on components within the evaporator compartment.
For the location of components that require maintenance, see the appropriate pages of the submittal
drawing DPN004597 included in the
on page 69. Plan access through at least one
door to allow for removal of evaportor coil. See notes on DPN004602 for recommended clearance.
NOTICE
Risk of equipment damage. The evaporator access panel cannot be opened while the exterior
man door is closed.
CAUTION: Risk of low-hanging panels. Can cause injury or equipment damage. Wear
appropriate, OSHA-approved PPE when entering and working within the enclosure.
8.2 Filters
NOTICE
Risk of improper filter installation. Can cause filter collapse and airflow reduction.
Pleat direction is non-standard. Use only short-pleat filters (see
). Long-pleat
filters are subject to collapse at high airflows.
To maximize the performance and reliability of the equipment, use only Vertiv filters. Contact your Vertiv
representative to order replacement filters.
Verify that filters are installed and positioned so the air-flow direction marked on the filter is the same
direction as unit air flow.
Unit Size
Filter Size, Width x Length, in. (mm)
Number of Filters
4 in. (102 mm) Filter Option,
MERV 8, MERV 11 or MERV 13
DP060
25 x 16 (635 x 406)
1
25 x 20 (635 x 508)
2
Table 8.1 Filter Quantities
8.2.1 Filter-replacement
1. Disconnect power from the unit.
2. Open the front access panel, locate the filter above the electric panel, and slide the filter out
the front of the unit.
3. Replace with new filter—install the filter in the proper direction of the airflow.
4. Test the operation of the filter clog switch.
The unit panels must be in place and closed to find this point.
Vertiv | Liebert® DSE060™ Installer/User Guide
32
Содержание Liebert DSE060
Страница 1: ...Liebert DSE Packaged Solution Thermal Management System Installer User Guide 60 kW 15 ton Capacity...
Страница 18: ...Vertiv Liebert DSE060 Installer User Guide 18 This page intentionally left blank...
Страница 22: ...Figure 4 3 Typical Center Line of Fork Pockets Vertiv Liebert DSE060 Installer User Guide 22...
Страница 26: ...Vertiv Liebert DSE060 Installer User Guide 26 This page intentionally left blank...
Страница 30: ...Vertiv Liebert DSE060 Installer User Guide 30 This page intentionally left blank...
Страница 66: ...Vertiv Liebert DSE060 Installer User Guide 66 This page intentionally left blank...
Страница 68: ...Vertiv Liebert DSE060 Installer User Guide 68 This page intentionally left blank...
Страница 70: ...Vertiv Liebert DSE060 Installer User Guide 70 This page intentionally left blank...
Страница 97: ...Vertiv Liebert DSE060 Installer User Guide...