Compressor Section
o
Check the oil level.
o
Check for oil leaks
o
Check the compressor mounts (springs/bushings).
o
Verify that the cap tubes are not rubbing.
o
Check/re-torque the wire connections (inside the compressor box).
o
Check the compressor operation (vibration/noise).
o
Check the crank-case heater fuses/operation.
o
Check for refrigerant leaks.
o
Suction pressure
Circuit #1
_______
Circuit #2
_______
o
Discharge pressure
Circuit #1
_______
Circuit #2
_______
o
Superheat
Circuit #1
_______
Circuit #2
_______
o
Low pressure switch cut out
Circuit #1
_______
Circuit #2
_______
o
Low pressure cut in
Circuit #1
_______
Circuit #2
_______
o
High pressure cut out
Circuit #1
_______
Circuit #2
_______
o
Amp draw
Circuit #1A
L1
L2
L3
Circuit #1B
L1
L2
L3
Circuit #2A
L1
L2
L3
Circuit #2B
L1
L2
L3
10 Preventive Maintenance Checklist
55
Содержание Liebert DA250
Страница 10: ...Vertiv Liebert DSE Thermal Management System Installer User Guide 6 This page intentionally left blank ...
Страница 14: ...Vertiv Liebert DSE Thermal Management System Installer User Guide 10 This page intentionally left blank ...
Страница 18: ...Vertiv Liebert DSE Thermal Management System Installer User Guide 14 This page intentionally left blank ...
Страница 44: ...Vertiv Liebert DSE Thermal Management System Installer User Guide 40 This page intentionally left blank ...
Страница 46: ...Vertiv Liebert DSE Thermal Management System Installer User Guide 42 This page intentionally left blank ...
Страница 56: ...Vertiv Liebert DSE Thermal Management System Installer User Guide 52 This page intentionally left blank ...
Страница 64: ...Vertiv Liebert DSE Thermal Management System Installer User Guide 60 This page intentionally left blank ...
Страница 89: ...Vertiv Liebert DSE Thermal Management System Installer User Guide 62 This page intentionally left blank ...
Страница 90: ...Vertiv Liebert DSE Thermal Management System Installer User Guide ...