Vertiv I Liebert ITA2 30kVA I Manual
b) Press the
or
key to select and set corresponding parameters (taking 'Output' as
an example). As shown in Figure 2-
19
.
Output
Battery
Monitor
Voltage selection
220V
Startup on bypass
Disable
Frequency selection
Auto,Byp...
Inverter sync range
+3.0Hz
Bypass voltage lower li...
-40%
Bypass frequency range
+10Hz
Bypass voltage upper li...
+20%
-
-
System
Output
Battery
Monitor
System
Run mode
Normal
Figure 2-19 Output interface
4. After setting corresponding parameters, press the power button for two seconds, and the
LCD prompts a dialogue box shown in Figure 2-2
0
.
Status
Settings
Control
Log
About
Maintain
Confirm
No
Yes
Turn on UPS?
Figure 2-20 Turning on UPS
After selecting 'YES', the run indicator (green) blinks, the inverter starts, and the run indicator
turns on.
5. Measure whether the inverter output voltage is normal.
6. If the battery is not connected, the alarm indicator is yellow. If the battery is connected, the
alarm indicator turns off.